Output Phase Failure Detection - Toshiba TOSVERT VF-PS1 Instruction Manual

Variable torque inverter
Hide thumbs Also See for TOSVERT VF-PS1:
Table of Contents

Advertisement

3) Selecting the operation of the FL relay
Using the output terminal selection parameter, you can specify whether or not to operate the FL relay.
(output terminal selection 3) =
(output terminal selection 3) =
[Parameter setting]
Title
Emergency stop
Emergency DC braking control time
DC braking current
(Example of terminal assignment): Assigning the emergency stop function to the S3 terminal.
Title
Input terminal function selection
7(S3)
Note 1: Emergency stopping via the specified terminal is possible, even during operation panel operation.
Note 2: If
=
braking time
4) Emergency stopping from the operation panel is possible
Pressing the STOP key on the operation panel twice enables emergency stop.
(1) Press the STOP key ———— "
(2) Press the STOP key again — If

6.26.4 Output phase failure detection

: Output phase failure detection mode selection
• Function
This parameter detects inverter output phase failure. If the inverter detects an open phase failure, the
tripping function and the FL relay will be activated. At the same time, the trip information
be displayed.
Detection errors may occur for special motors such as high-speed motors.
= : No tripping
= : With the power on, the phase failure detection is enabled only at the start of the first operation. The
inverter will trip if the inverter detects an open phase failure.
= : The inverter checks for output phase failures each time it starts operation. The inverter will trip if the
inverter detects an open phase failure.
= : The inverter checks for output phase failures during operation. The inverter will trip if the inverter
detects an open phase failure.
= : The inverter checks for output phase failures at the start of and during operation. The inverter will trip if
the inverter detects an open phase failure.
= : If the inverter detects an open phase failure in every phase, it does not trip but restarts operation when
every phase is reconnected.
The inverter does not check for output phase failures when restarting after a momentary power failure.
This function (
Note: A check for output phase failures is made during auto-tuning 1 (
this parameter
[Parameter setting]
Title
Output phase failure
detection mode
selection
(default): Operates the FL relay in the event of an emergency stop.
: Does not operate the FL relay in the event of an emergency stop.
Function
Function
(Emergency DC braking) and DC braking is not required for normal stopping, set the DC
to
[s].
" will blink.
(Emergency stop) =
trips) according to the setting.
If " " is displayed an error detection signal (FL) is issued (FL is activated).
= ) doesn't operate at 200V-55kW/75kw and 400V-90kW and above models.
.
Function
:Deselect
:At starting (only one time after power is turned on)
:At starting (each time power is turned on)
:During operation
:At starting + during operation
:Output cut-off detection enabled
F-49
Adjustment range
:Coast stop
:Deceleration stop
:Emergency DC braking
~
sec.
~
%
Adjustment range
~
~ , the motor makes an emergency stop (or
= ,
), regardless of the setting of
Adjustment range
E6581386
Default setting
Setting value
(Emergency
stop)
6
will also
Default setting