3) Common specification
Item
Control system
Sinusoidal PWM control
Output voltage adjustment Main circuit voltage feedback control. (Switchable between automatic adjustment/fix/control off)
Setting between 0.01 to 500Hz. Default max. frequency is set to 0.01 to 60Hz.
Output frequency range
Maximum frequency adjustment (30 to 500Hz)
Minimum setting steps of
0.01Hz: operation panel input (60Hz base),
frequency
0.03Hz: analog input (60Hz base, 11 bit/0 to 10Vdc)
Analog input: ±0.2% of the maximum output frequency (at 25±10°C)
Frequency accuracy
Digital input: ±0.01%±0.022Hz of the output frequency
V/f constant, square reduction torque control, automatic torque boost, vector calculation control, base
Voltage/frequency
frequency adjustment 1 and 2 (25 to 500Hz), V/f 5-point arbitrary setting, torque boost adjustment (0 to
characteristics
30%), start frequency adjustment (0 to 10Hz), stop frequency adjustment (0 to 30Hz)
3kΩ potentiometer (possible to connect to 1k to 10kΩ-rated potentiometer)
0 to 10Vdc (input impedance Zin: 30kΩ)
Frequency setting signal
0 to ±10Vdc (Zin: 22kΩ)
4 to 20mAdc (Zin:242Ω)
Terminal board base
The characteristic can be set arbitrarily by two-point setting. Compliant with 6 types of input; analog input
frequency
(RR, VI/II, RX, AI1, AI2), and pulse input. (*AI1, AI2, pulse input: optional)
Frequency jump
3 places. Setting of jump frequency and width.
Upper and lower limit
Upper limit frequency: 0 to max. frequency, lower limit frequency: 0 to upper limit frequency
frequencies
200V-45kW and below, 400V-75kW and below : Adjustable between 1.0k to 16kHz
PWM carrier frequency
200V-55kW and above, 400V-90kW and above: Adjustable between 2.5k to 8kHz
PID control
Adjustment of proportional gain, integral time, differential time and delay filter
Acceleration/deceleration
0.01 to 6000 sec. Selectable from among acceleration/deceleration. times 1 and 2. Automatic
time
acceleration/deceleration function. S-pattern acceleration/deceleration 1 and 2 pattern adjustable.
Adjustment of braking start frequency (0 to 120Hz), braking (0 to 100%) and braking time (0 to 20 sec.).
DC braking
With emergency stop braking function and motor shaft fix control function.
Forward run/reverse run
With F-CC closed to forward run, with R-CC closed to reverse run, with both closed to reverse run. With
[Note 1]
ST-CC opened to coast stop. Emergency stop by panel operation or terminal board.
Jog run
Jog mode, if selected, allows jog operation from the operation panel
[Note 1]
Jog run operation by terminal board is possible by setting the parameters.
By changing the combination of open/close between S1, S2, S3, RR/S4-CC, set frequency + 15-speed
Preset speed operation
operation.
[Note 1]
Selectable between acceleration/deceleration time, torque limit and V/f by set frequency.
Capable of restarting after a check of the main circuit elements in case the protective function is
Retry
activated. Max. 10 times selectable arbitrarily. Waiting time adjustment (0 to 10 sec.)
Soft stall
Automatic load reduction control at overloading. (Default: OFF)
Cooling fan ON/OFF
The cooling fan will be stopped automatically to assure long life when unnecessary.
Operation panel key
Key prohibition selectable between STOP key only, MODE key only, etc. All key operations can be
operation ON/OFF control
prohibited.
Regenerative power
Possible to keep the motor running using its regenerative energy in case of a momentary power failure.
ride-through control
(Default: OFF)
Auto-restart operation
Possible to restart the motor in coasting in accordance with its speed and direction. (Default: OFF)
Commercial inverter
Possible to switch operation by commercial power source or inverter
switching
When two or more inverters are used to operate a single load, this function prevents load from
Drooping function
concentrating on one inverter due to unbalance.
Override function
External input signal adjustment is possible to the operation frequency command value.
Stall prevention, current limit, overcurrent, overvoltage, short circuit on the load side, ground fault on the
load side [Note 6], undervoltage, momentary power failure (15ms or more), non-stop control at
Protective function
momentary power failure, overload protection, arm overload at starting, overcurrent on the load side at
starting, overcurrent and overload at dynamic braking resistance, overheat, emergency stop
Electronic thermal
Switchable between standard motor/constant torque VF motor, adjustment of overload protection and
characteristic
stall prevention level.
Reset by 1a contact closed (or 1b contact opened), or by operation panel. Or power source OFF/ON.
Reset
This function is also used to save and clear trip records.
(Continued overleaf)
Specification
L-3
E6581386