Toshiba TOSVERT VF-PS1 Instruction Manual page 296

Variable torque inverter
Hide thumbs Also See for TOSVERT VF-PS1:
Table of Contents

Advertisement

(Continued)
4-digit
and
7-segme
nt LED
LED
Power Removal safety function
Input/output terminal input
function
Sink/source switching
Failure detection signal
Low speed/speed reach
signal output
[Note 2]
Upper/lower limit
frequency signal output
[Note 2]
Output for frequency
meter/
Output for ammeter
[Note 3]
Pulse train frequency
output
Communication function
Use environments
Ambient temperature
Storage temperature
Relative humidity
Vibration
Note 1: 15 contact input terminals (of which 8 are options) are programmable contact input terminals, and they make
it possible to arbitrarily select from about 80 types of signals.
Note 2: Programmable ON/OFF output terminals make it possible to arbitrarily select from about 180 types of signals.
Note 3: Programmable analog output terminals make it possible to arbitrarily select from about 50 types of signals.
12
Note 4: 200V class 0.4~45kW, 400V class 0.75~75kW: When using inverters where the ambient temperature will
200V class 55~90kW, 400V class 90~630kW:
Note 5: Inverters, 18.5kW or greater, do not have wiring port covers. They have large openings, but there is no space
to bend the external cables inside the unit.
Note 6: This function protects inverters from overcurrent due to output circuit ground fault.
Item
Stall prevention during operation, overload limit, overload, undervoltage on power source side, DC circuit
Alarms
undervoltage, setting error, in retry, upper limit, lower limit.
Overcurrent, overvoltage, overheat, short circuit on the load side, ground fault on the load side, inverter
overload, arm overcurrent at starting, overcurrent on the load side at starting, CPU error, EEPROM error,
Causes of
RAM error, ROM error, communication error, (dynamic braking resistor overcurrent/overload),
failures
(emergency stop), (undervoltage), (low current), (overtorque), (motor overload), (input phase failure),
(output phase failure)
The items in the parentheses are selectable.
Operation frequency, operation frequency command, forward run/reverse run, output current, DC
voltage, output voltage, compensated frequency, terminal board input/output information, CPU version,
past trip history, cumulative operation time, speed feedback, torque, torque command, torque current,
Monitoring
exiting current, PID feedback value, motor overload factor, inverter overload factor, PBR overload factor,
function
PBR load factor, input power, output power, peak output current, peak DC voltage, RR/S4 input, VI/II
input, RX input, AI1 input, AI2 input, FM output, AM output, expansion I/O card option CPU version,
integral input power, integral output power, communication option reception counter, communication
option abnormal counter
Display of optional units other than output frequency (motor speed, line speed, etc), current ampere/%
Free unit display
switch, voltage volt/% switch
Automatic edit
Searches automatically parameters that are different from the standard default setting parameters. Easy
function
to find changed parameters.
User default
User parameter settings can be saved as default settings. Allows to reset the parameters to the
setting
user-defined parameter settings.
Charge display
Displays main circuit capacitor charging.
Built-in Power Removal safety function which complies with EN954-1 category 3 and IEC/EN 61508-1
SIL2.
Possible to select positive logic or negative logic with programmable input/output terminal function menu.
[Note 1] [Note 2]
(Default setting: positive logic)
Possible to switch between minus common (CC) and plus common (P24) for control terminal.
(Default setting: minus common (CC))
1c contact output (250Vac-2A-cosФ=1, 250Vac-1A-cosФ=0.4, 30Vdc-1A)
Open collector output (24Vdc, max. 50mA, output impedance: 33Ω)
Open collector output (24Vdc, max. 50mA, output impedance: 33Ω)
Analog output. 1mAdc full-scale DC ammeter or 7.5Vdc-1mA voltmeter
Open collector output (24Vdc, max. 50mA)
RS-485 standard 2-channel equipped (connector: modular 8P)
CC-Link, DeviceNet, PROFIBUS-DP, Modbus TCP, APOGEE FLN, L
Modbus Plus are optional.
Indoor use. Altitude: 3000m or less (current reduction necessary if 1000m or more.) Place not exposed
to direct sunlight and free of corrosive, explosive gases, dust and oil mist.
-10 to +60°C (Remove the upper cover if 40°C or more, max. 60°C) [Note 4]
-25 to +70°C
5 to 95% (free from condensation)
2
5.9m/s
{0.6G} or less (10 to 55Hz) (Compliant with JIS C60068-2-6)
Specification
rise above 40°C, remove the covers on top of them, or when
using them where the ambient temperature will rise above
50°C, remove the covers on top of them and lower the output
current.
When using inverters where the ambient temperature will
rise above 45°C, operate each inverter at a current lower
than the rated one.
L-4
E6581386