This means that, following an immediate start of a new measurement, the
result and curve files will not be immediately transmitted. So you should only
choose this method if very fast processes have to be monitored and the
results and curves are merely used for spot checks.
Started
Ready
Running
Result valid
Process OK
Fig. 8.2: Sequence optimized to the process

8.3 Transducer test

The transducer test can be triggered via the digital input or via the bus signal.
At low filter limit frequencies, the filter settling time must be waited before the
test. A pulse of minimum 5 ms duration at the digital input is necessary for the
transducer test. The result is typically available another 10 ms later.
A2392−5.0 en
Start (ext. signal "Start"
or condition fulfilled)
Stop (condition fulfilled) or end, if ext. signal for end
condition is used and signal "End" is active
Offline evaluation
Time until stop (follow-up time, only possible when using
internal stop condition)
Measurement
Initialization (typ. 25 ms)
Reaction time (typ. 2 ms for external signal)
(internal) end condition fulfilled
(with ext. signal "End" this is
already fulfilled)
Signal is only set, if end
conditions are fulfilled and
data is saved to RAM
Save to MMC/PC
Save (to RAM)
67