HBM MP85A Operating Manual

HBM MP85A Operating Manual

Twin-channel-amplifiers
Hide thumbs Also See for MP85A:
Table of Contents

Advertisement

A2392−5.0 en
Operating Manual
Twin-channel-
Amplifiers
Modules
MP85A, MP85ADP
FASTpress
MP85A-S, MP85ADP-S
EASYswitch

Advertisement

Table of Contents
loading

Summary of Contents for HBM MP85A

  • Page 1 Operating Manual Twin-channel- Amplifiers Modules MP85A, MP85ADP FASTpress MP85A-S, MP85ADP-S EASYswitch A2392−5.0 en...
  • Page 3: Table Of Contents

    ....... . . MP85A(DP)(-S) installation/removal (basic diagrams) ...
  • Page 4 ......MP85A process controller in machine control ....
  • Page 5: Safety Information

    • MP85A-S • MP85ADP-S The designation MP85A process controller will be used for all devices in this manual. If text/data refers only to specific devices, this will be clearly indicated in the text and one of the above designations used.
  • Page 6 − When cleaning, ensure that no liquid gets into the device or connections. Residual risks The scope of supply and performance of the MP85A process controller covers only a small area of measurement technology. In addition, equipment plan- ners, installers and operators should plan, implement and respond to the safety engineering considerations of measurement technology in such a way as to minimize remaining dangers.
  • Page 7 MP85ADP, PROFIBUS DP) must be shielded, twisted-pair lines. The trans- ducer cables must also be shielded. The shield of each transducer cable must be connected at the MP85A process controller via as short a line as possible (t5 cm) and a flat connector (4.8 mm; “Faston”).
  • Page 8 Conversions and modifications The MP85A process controller must not be modified from the design or safety engineering point of view except with our express agreement. Any modifica- tion shall exclude all liability on our part for any damage resulting therefrom.
  • Page 9 MP85A process controller It is also essential to comply with the legal and safety requirements for the application concerned during use. The same applies to the use of accessories. Maintenance and repair work on an open device with the power on must only be carried out by trained personnel who are aware of the dangers involved.
  • Page 10: Introduction

    Function module kit for creating separate interfaces on operator panels via Ethernet under Windows XP, Windows CE and WindowsMobile • EASYmonitor CE: Production software (demo-version, for operation on Touch-Panels under Windows CE) • INDUSTRYmonitor (demo version): Production software for operation on Touch-Panels with max. 12 MP85A process controllers A2392−5.0 en...
  • Page 11: General Information

    • Ethernet crossover cable, 2 m, (1-KAB239-2) 1.2 General information The MP85A process controller from the PME product line is a twin-channel amplifier, suitable for connecting transducers of different technologies. The MP85ADP and MP85ADP-S also have a PROFIBUS interface in addition to the ETHERNET and CAN interfaces.
  • Page 12: About This Documentation

    − a separate operating manual with an object dictionary and an interface description for Ethernet, CAN and PROFIBUS communication − a quick start guide for fast commissioning of the MP85A process controller and all software modules − a quick start guide for the whole FASTpress suite, i.e. for all software modules and the MP85A process controller A2392−5.0 en...
  • Page 13: Mp85A(Dp)(-S) Installation/Removal (Basic Diagrams)

    MP85A process controller MP85A(DP)(-S) installation/removal (basic diagrams) 2.1 Mechanical installation Fig. 2.1: Mounting on a DIN rail Fig. 2.2: Removal CAUTION The DIN rail must be connected to grounded conductor potential A2392−5.0 en...
  • Page 14: Connecting Several Devices

    MP85A process controller Fig. 2.3: Fitting a second spring for a more stable MP85A process controller mounting on the DIN rail 2.2 Connecting several devices Flat ribbon cable female connector Subsequent devices are interconnected via this Color-coding on connector. Pin 1...
  • Page 15: Electrical Connection

    MP85A process controller Electrical connection WARNING Comply with the safety instructions before starting up the device. 3.1 Overview of MP85A/MP85A-S functions Local connection of CAN bus, supply voltage and synchronization between modules Screw terminal 1: Voltage supply and CAN bus,...
  • Page 16: Overview Of Mp85Adp/Mp85Adp-S Functions

    MP85A process controller 3.2 Overview of MP85ADP/MP85ADP-S functions Local connection of CAN bus, supply voltage and synchronization between modules Screw terminal 1: Voltage supply and CAN bus, synchronization LED 1 Screw terminal 2: (same assignment as screw terminal 1) LED 2...
  • Page 17: Supply Voltage And Control Inputs/Outputs

    IN = digital input OUT = digital output IN 4 IN 5 Should the mains power fail in the MP85A process controller, CAUTION all control outputs will be set to 0 V. Fig. 3.1: Screw terminal assignment The screw terminals are coded to stop them being fitted into the wrong socket.
  • Page 18: External Supply Voltage For Control Outputs

    • at screw terminal 3: control outputs 1...4 • at screw terminal 4: control outputs 5...8 (MP85A(-S) only) The control outputs must be supplied with an external voltage (ground and 24 V) via screw terminal 3. This external voltage is electrically isolated from the measurement ground.
  • Page 19: Transducer

    MP85A process controller 3.4 Transducer Two transducers can be connected to screw terminals 5 and 6, independently of one another. The two measurement channels are parameterized using the PME Assistant (menu: Transducer). 3.4.1 Synchronization of carrier frequencies Synchronization prevents interferences occurring due to small differences in the carrier frequencies of the individual amplifiers, i.e that amplifiers disturb...
  • Page 20: Sgs, Displacement Transducers, Potentiometric And Lvdt Sensors

    MP85A process controller 3.4.2 SGs, displacement transducers, potentiometric and LVDT sensors In “carrier-frequency amplifier” mode, the following transducer types can be connected: MP85A(-S) MP85ADP(-S) Screw terminals 5 and 6 for transducer connection SENSOR X SENSOR Y SG and inductive full bridges,...
  • Page 21 Otherwise EMC protection is not ensured. CAUTION Line break detection MP85A process controllers have line break detection for the connected trans- ducers. The excitation voltage lines and the measurement signal leads are monitored. With sense leads, a wire break is only reported as a fault if both lines are broken;...
  • Page 22: Incremental, Ssi And Dc Sensors

    MP85A process controller 3.4.3 Incremental, SSI and DC sensors In “Incremental encoder, SSI transducer or DC voltage transducer” mode, the following transducer types can be connected: MP85A(-S) MP85ADP(-S) Pulse counters, incremental transducers (symmetrical signals, TTL level, 5V) Ground Measurement signal F1 (+), 0°...
  • Page 23 An internal or external power supply can be selected via switch S1. The device must be open to do this (see Chapter 4). • Transducer supplied from MP85A process controller: Transducer supply voltage 5 V "10%, 150 mA max. (for both channels together).
  • Page 24: Piezoelectric Measurement Chains

    MP85A process controller. The charge amplifier is supplied externally with 24 VDC and is available from Pin 7 and 8 of the screw terminals 5 and 6 of the MP85A process controller (see Chapter 3.4.3, Active sensors, Fig. 3.7).
  • Page 25 MP85A process controller from hardware version V1.07. When operating without TEDS, the measurement ground (charge amplifier, Pin 6) must be connected directly to Pin 3 of the MP85A process controller. The yellow cable (TEDS) is therefore not required.
  • Page 26 MP85A process controller Sensor x/y (Screw terminals 5 and 6) MP85A process controller digital OUT (Reset piezo sensor); screw terminal 3 or 4 (output) Operating on a SELV circuit (separated extra-low voltage) Fig. 3.9: Connection of the piezoelectric charge amplifier CMA/CMD...
  • Page 27: Teds-Transducers (Electronic Data Sheet)

    Fig. 3.10: MP85A process controller with TEDS technology 3.5.2 Parameterization with TEDS If a transducer with TEDS, containing the parameterization data for a sensor, is connected, this can be used to parameterize the MP85A process controller automatically. When the MP85A process controller is activated, it automatically detects whether a TEDS is connected.
  • Page 28: Interfaces

    The available units match the selection list provided by the PME Assistant. CAUTION If several transducers are connected to an MP85A amplifier input in parallel, their TEDS data cannot not be used as neither the error-free reading out of parallel connected TEDS is ensured nor can a summation of the individual parameters take place.
  • Page 29: Ethernet Interface

    MP85A process controller 3.6.1 Ethernet interface An RJ45 socket for Ethernet connection is located underneath the MP85A process controller as standard. RJ45 Fig. 3.11: Ethernet connection The device can also be integrated into an existing Ethernet network. It supports speeds of 10 Mbit/s and 100 Mbit/s. The transmission speed is auto- matically adapted to the existing network.
  • Page 30: Can Interface

    The CAN bus needs a termination resistor of 120 Ω on the first and last bus node The maximum number of termination resistors the bus cable can have is two. The MP85A process controller has an integrated termination resistor, which is activated by toggle switch S2. Low High Device 1 Fig.
  • Page 31: Profibus Interface (Mp85Adp/Mp85Adp-S Only)

    MP85A process controller CAN-High CAN-Low CAN connection as per Fig. 3.13 First device in the bus cable Last device in Connect the termination the bus cable resistor here (toggle Do not connect the switch) Connect the termination resistor termination resistor here (toggle switch) Fig.
  • Page 32 MP85A process controller Installation: • Connect the MP85ADP(-S) to a 24 V supply voltage and use the keyboard or the Setup program to set the required PROFIBUS address. • Connect the PROFIBUS line to the MP85ADP(-S). Make sure that termina- tion resistors are connected on the first and last PROFIBUS nodes (there is usually a slide switch on the housing of the PROFIBUS plug for this).
  • Page 33: Switch Settings / Replacing The Battery

    5 V internal sensor supply voltage. NOTE The housing needs to be opened for this switchover. Therefore a change must be made before the MP85A(DP) is mounted. To set switch S1, proceed as shown in Fig. 4.1. Unscrew the...
  • Page 34 Fig. 4.3: Switch for the CAN bus termination resistor (basic diagram) Replacing the battery The MP85A process controller has a real-time clock, which is fed by a CR2032-type lithium battery. It can be removed from the battery holder and replaced at the point shown in Fig. 4.4. The battery should be replaced about every five years.
  • Page 35 MP85A process controller Battery position − Fig. 4.5: Correct battery position The buffer battery is only required for the device-internal real-time clock. The device functions are not affected by the battery. However, the time is also saved with the curve and results files. The cor- rect time and data should therefore be set in the device (PME Assistant: menu: Basic settings).
  • Page 36: Starting Up/Setting Up Mode

    To prepare the MP85A process controller for a measurement task, the following requirements must be met and the relevant steps taken: • You require an MP85A process controller and either the PME Assistant or INDUSTRYmonitor program. • The hardware must be set up: Transducer, MP85A process controller, PC with software (from Section 5.2).
  • Page 37: Operation

    5.1.1 Device settings, measured values, process status, PROFIBUS, memory cards, error types, firmware update, device backup The MP85A process controller device display shows the measured values and status information for measurement channels, process status, digital inputs/outputs and parameter set backup; devices with PROFIBUS interface also display the PROFIBUS status.
  • Page 38 The last process was not OK • Started A process has been started and not yet finished 3. Status of the digital inputs and outputs The MP85A(-S) has 5 inputs and 8 outputs. The MP85ADP(-S) has 1 input and 4 outputs. • Input not set...
  • Page 39 MMC or SD cards must be format- ted with FAT16, not with NTFS, otherwise they will not be recognized by the MP85A process controller. If necessary, reformat the card. The MMC/SD card should be defragmented or reformatted at regular intervals to optimize the access times.
  • Page 40 6. Kinds of error During measurement, the ! character in the status field (in measuring mode) indicates an MP85A process controller error. Errors are displayed successively (can be reached using − − ERROR x (relative to the SENSOR X screw terminal) −...
  • Page 41 We recommend saving the device settings (device backup) before any updates. 8. Device backup All MP85A process controller settings can be saved to MMC/SD card via the integrated keyboard and then, e.g. transferred to another MP85A process controller. Using the device menu, all 31 Flash parameter sets, including all interface settings of the MP85A process controller, can be saved to the memory card A2392−5.0 en...
  • Page 42: Overview Of All Groups And Parameters

    MP85A process controller as a backup (“S-Status Save”) and reloaded into the MP85A process controller where necessary. When loading, you can select whether loading should take place without interface parameters (“S-Status Restore”) or with interface parameters (“S-Status Load-Com”), see Chapter 5.1.3. Confirm the action by pressing the SET button.
  • Page 43 System-state: From firmware version 2.22, you can save the MP85A process controller settings to an MMC/SD card or e.g. load them into another MP85A process controller. “S-Status Restore” restores all settings, “S-Status Load-Com” restores all settings except the addresses (CAN/Ethernet/PROFIBUS).
  • Page 44: Setting Parameters On The Device

    MP85A process controller 5.1.3 Setting parameters on the device Measured value 2 secs Groups CAN bus PROFIBUS ETHERNET − MAC address 10kB ↑ Baudrate +/− 20kB 50kB IP-Adr.1 100 kb 125 kb 250 kb IP-Adr.2 Address 500 kb − 1000 kb IP-Adr.3...
  • Page 45: Hardware Setup

    MP85A process controller Groups SYSTEM-STATE ADD. FUNCTION MEAS. MODE − − ↑ Ampl.Type Backup Save? +/− Save PrgVers Backup Restore Meas. value SrNo Backup Load-Com HW vers. − − ↓ ↑ SD/MMCLo 0 − 31 +/− (ad) Back to Main Back to Main 5.2 Hardware setup...
  • Page 46: Establishing The Ethernet Connection

    5.2.2 Establishing the Ethernet connection For an MP85A process controller to communicate with the PC, the device must be connected to the PC. Use an Ethernet crossover cable (1-KAB239-2) for direct connection. The connection (RJ45 socket) is located underneath the MP85A process controller.
  • Page 47: Connecting The Can Adapter (Usb)

    Assistant and when the USB to CAN adapter is connected. 5.3 Installing the PME Assistant software The PME Assistant is installed using the supplied system CD. The latest version can also be found on the HBM website: www.hbm.com −> Support −> Software-/Firmware-Downloads. System requirements...
  • Page 48: Pme Assistant Operation

    IP address or setting a new one. The address cannot be assigned automatically via DHCP. So you must • make sure that the IP address of the MP85A process controller differs from the address of the network being used in max. one segment. A2392−5.0 en...
  • Page 49: Using The Usb Interface

    The baudrate in the CAN network must be the same. In the delivery • condition, the baudrate of the MP85A process controller is set to 1 MBit/s. • If you select “Use as standard”, this network will be chosen automatically the next time the system starts up.
  • Page 50: Automatic Version Recognition

    PME Assistant, the following message appears: The firmware of the device can be determined via the display of the MP85A, PME Assistant or the INDUSTRYmonitor program. NOTE The latest PME Assistant is always compatible with all MP85A(DP)-(S) devices.
  • Page 51: Offline Operation

    5.7 Offline operation In offline operation, the PME Assistant can be used without a connected MP85A process controller to create a device setting (parameter set) and save it in XML format to PC. The device setting can later be transferred to the MP85A process controller.
  • Page 52: Methods Of Measurement

    When measurement starts, the measured quantities acquired by the sensors are written as an x/y value pairs with a time stamp to the internal MP85A process controller memory and rated as OK or NOK by means of defined windows, an envelope curve or a tolerance band.
  • Page 53: Classification

    MP85A process controller Fig. 6.2: Time-driven process curve determination 6.2 Classification Classifying X or Y Measured quantities on channel X, such as length, thickness and diameter or channel Y, such as force, weight, torque, etc., can be divided into 5 groups per window.
  • Page 54: Masking Out External Tolerances

    Fig. 6.4: Reference points for X relative reference of evaluation elements 6.5 Evaluation criteria The MP85A process controller has different window types to allow a universal evaluation of the various curve shapes using window techniques. Any mix of these window types can be used for each measurement curve. An envelope curve is available if the entire process is to be monitored without a gap.
  • Page 55 MP85A process controller Error during thread-in ! Force too great ! Real-time signal “Withdraw press” Fig. 6.6: Online window Process window This window type checks the course of a curve in the window area. The curve must run through the window as defined from the entry side to the exit side, without violating any of the other window limits.
  • Page 56 MP85A process controller Thresholds Thresholds monitor the process continuously in very restricted ranges. The thresholds can be positioned vertically or horizontally. As an option for machine safety, these evaluation elements can also monitor the process in real time and signal the control via a digital output or the field bus.
  • Page 57 MP85A process controller Fig. 6.11: Tolerance band Limit monitoring From firmware version 2.22 and higher, the limit values can also be included in the total result for process monitoring. This allows, e.g. minimum and maximum values to be monitored at the start and/or end of a process. This option is particularly useful in the evaluation methods “Envelope curve”...
  • Page 58: Measurement Programs (Parameter Sets)

    MP85A process controller 6.6 Measurement programs (parameter sets) A total of 31 measurement programs can be activated from the MP85A process controller’s internal (flash) memory for 31 different workpieces. A measurement program comprises a workpiece-specific parameter set consisting of the settings of the amplifier for the sensor technology, measure- ment acquisition and storage, function assignments of the digital inputs/ outputs and the evaluation methods.
  • Page 59 If the parameter sets from the internal Flash-EPROM are used, the system parameters are identical for all 31 Flash parameter sets and only present once in the MP85A process controller. If parameter sets from the MMC/PC card or from PC are used, the system parameters are a component of the respective parameter set and can therefore be different.
  • Page 60: Switch Checker With Mp85A(Dp)-S Easyswitch

    The functions for switch and haptic tests are only available in an MP85A(DP)-S EASYswitch (switch test version). 7.1 Switch test All the switching characteristics are recorded by the MP85A(DP)-S EASY- switch and evaluated according to specific features, such as actuating force, release force, differential force and differential travel.
  • Page 61 • At screw terminal 3: Control input 1 • At screw terminal 4: Control inputs 2 … 5 (MP85A/MP85A-S only) An external reference potential ( ), to which the control input signals relate, must be connected for the switch test processes.
  • Page 62: Haptic Check

    If the switch is defective, limit force switch off is implemented with a reaction time of approx. 2 ms. Further information can be found in the online help of the PME Assistant and the MP85A process controller interface description. A2392−5.0 en...
  • Page 63: Communication With A Control System

    Digital inputs/outputs and the CAN, PROFIBUS-DP and Ethernet digital inter- faces are available for embedding into a machine control. Both these cases access the same MP85A process controller device functionality (object table). Firstly, control commands can be exchanged between the MP85A process...
  • Page 64 The next pro- cess can only be started after switchover which can take up to 200 ms, the MP85A pro- cess controller is only ready for measurement after switchover. As long as the signal is ac-...
  • Page 65: Test Process Sequence Over Time

    MP85A process controller Description MP85A(DP)(-S) control input Store/clear statistics Stores the statistical data present in the RAM in the Flash EPROM Switch test 1 ... 5 For MP85A(DP)-S only: Specify which inputs must be used for the test with regards to a switch test. The inputs must...
  • Page 66 If the process data (curves and results) cannot be stored (because the memory is full or faulty, for example), the next process cannot be star- ted, as the MP85A process controller does not enable the Ready signal. When saving data externally to a PC, the PME Assistant or INDUSTRY- monitor must remain open.
  • Page 67: Transducer Test

    MP85A process controller This means that, following an immediate start of a new measurement, the result and curve files will not be immediately transmitted. So you should only choose this method if very fast processes have to be monitored and the results and curves are merely used for spot checks.
  • Page 68: Zero Balance

    It can be helpful, particularly during start up or service, to check the system components and processes downstream of the digital outputs through simula- tion and activation. The digital outputs of the MP85A process controller can be activated/deactivated via software commands for this purpose.
  • Page 69: Parameter Sets (Measurement Programs)

    1 again. 8.6 Parameter sets (measurement programs) The MP85A process controller has the option to use 31 different measure- ment programs (parameter sets) and store them power failsafe in internal flash memory. Another 1000 measurement programs can be saved to the optional memory card (MMC/SD card).
  • Page 70 MP85A process controller (Level change with Bit0 ... Bit4) Load parameter set Duration of switchover Typ. < 200 ms Parameter set is loading Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Active parameter set A2392−5.0 en...
  • Page 71: Evaluation/Storage Process Times

    − the number of evaluation criteria (tolerance window) − whether process data are to be stored (OK only, NOK only, all) − whether several MP85A process controllers should be operated in network (mains load) − the performance of the storage medium Some of these points can be specified via the PME Assistant or INDUSTRY- monitor programs (menu: Set evaluation parameters and Data storage).
  • Page 72 PLC machine control The following table shows the times that are approximately required when the MP85A process controller exchanges cyclical data with a PLC via PROFI- BUS, saves data to the MMC/SD card or transmits the data via Ethernet. With INDUSTRYmonitor software running on the PC.
  • Page 73: Process Data Storage/Production Data Management

    (cyclical data also exchanged via PROFIBUS) ment in s (approx.) 1 x MP85A process controller, 500 measurement points, save curves and results to MMC/SD card 3 x MP85A process controller, 600 measurement points, save curves and results to MMC/SD card 1 x MP85A process controller, 500 measurement points, output curves 4 −...
  • Page 74 This enables efficient production data management. The information is transmitted to the MP85A process controller via the PME Assistant, the INDUSTRYmonitor or the bus interface.
  • Page 75 MP85A process controller CAUTION A control/master with DPV1 functionality is required for transfer via PROFIBUS. The requisite objects are described in the MP85A process controller interface description. CAUTION Software such as the PME Assistant or INDUSTRYmonitor (HBM software for industrial applications) must be started to enable process curves and results to be stored on the PC/server.
  • Page 76: Display-And Control Options

    The black-and-white display is a backlit 1/4” VGA display. The device can also be connected to existing systems later on. No additional hardware or software is required to connect it directly to the CAN connection on an MP85A process controller.
  • Page 77: Fastpress Suite Software

    MP85A process controller 9.2 FASTpress Suite software The FASTpress Suite is measurement software for HBM devices of the PME product family. You can use it to perform a variety of measurement and control tasks quickly and easily, without the need for programming.
  • Page 78 (PME Assistant, EASYmonitor or INDUS- TRYmonitor) must be started on the target computer. However, only one application at a time may be used by the MP85A process controller, multi-master capability is not available. Further information can be found in the quick start guide “FASTpress Suite”.
  • Page 79: Error Messages/Operating State (Led Display)

    Error messages/operating state (LED display) Depending on the display mode, various error messages can be displayed instead of the measured value in the LCD display of the MP85A process controller (or the PME Assistant). Current errors are displayed continuously. Press the key to go to the “ERROR”...
  • Page 80 Operating state of the MP85A process controller: The LEDs indicate the operating states (ready for measurement, overflow, etc.) of the device. However, with the MP85ADP, it is the PROFIBUS state that is indicated, instead of the CAN state (as for the MP85A process controller). LED 1...
  • Page 81 Red LED Yellow Green Flashing Error state BD_SEAR, WT_PARM, WT_CONF states DATA_EX status Control LEDs for the Ethernet status are located underneath the MP85A process controller. LED Ethernet status Green LED Yellow LED Physical connection present − Transmit / receive data −...
  • Page 82 MP85A process controller Status A2392−5.0 en...
  • Page 83: Technical Support

    “Support − > Software/Firmware down- loads − > “Industrial Amplifiers”. Seminars HBM also offers seminars in your company or at our training center. You can learn everything there about the device and software programming. You can find further information under http://www.hbm.com...
  • Page 84 They are not to be understood as express warranty and do not constitute any liability whatsoever. Hottinger Baldwin Messtechnik GmbH Im Tiefen See 45 S 64293 Darmstadt S Germany Tel. +49 6151 803−0 S Fax: +49 6151 803−9100 Email: info@hbm.com www.hbm.com...

This manual is also suitable for:

Mp85adpMp85a-sMp85adp-s

Table of Contents