Code Parameter Name
Group 14
RELAY OUTPUTS
1401
1
RELAY OUTPUT
1402
2
RELAY OUTPUT
Group 32
SUPERVISION
3201
1
SUPERV
PARAM
3202
1
SUPERV
LIM LO
3203
1
SUPERV
LIM HI
3204
2
SUPERV
PARAM
3205
2
SUPERV
LIM LO
3206
2
SUPERV
LIM HI
Table 17 Analog output control.
Code Parameter Name
Group 01
OPERATING DATA
0133
3
SER LINK DATA
Group 15
ANALOG OUTPUT
1501
AO CONTENT
1503
AO CONTENT MAX
136
Setting for
Alternative
Standard
Settings
Modbus
0 =
e.g. 7 (
NOT SEL
...
OVER
7 =
1
SUPRV
OVER
8 =
1
SUPRV
UNDER
9 =
2
SUPRV
OVER
10 =
2
SUPRV
UNDER
...
31 =
STARTED
As above
e.g. 7 (
OVER
102 - 137
e.g. 131 (
LINK DATA
0 - 255
e.g. 100
0 - 255
e.g. 100
102 - 137
e.g. 132 (
LINK DATA
0 - 255
e.g. 100
0 - 255
e.g. 100
Setting for
Alternative
Standard
Settings
Modbus
0 - 255
-
102 - 137
e.g. 133
255
http://nicontrols.com
Function/Information
1
Relay output 1 function.
SUPERV
)
With the given setting, the relay 1 is
activated when supervised parameter 1
(given by parameter 3201) is above the
limit given by parameter 3203.
1
Relay output 2 function.
SUPERV
)
See above.
Number of supervised parameter 1. Any
SERIAL
1)
parameter of the group 1 OPERATING
DATA.
Lower supervision limit for supervised
parameter 1.
Upper supervision limit for supervised
parameter 1.
Number of supervised parameter 1. Any
SERIAL
2)
parameter of the group 1 OPERATING
DATA.
Lower supervision limit for supervised
parameter 2.
Upper supervision limit for supervised
parameter 2.
Function/Information
Controlling data for the analog output.
Directs the contents of parameter 133 to
the analog output.
Analog output scaling: upper limit (20 mA)
reached when value 255 is written to
parameter 133.
ACS 400 User's Manual