Group 34: Process Variables
Parameters of this group can be used to create custom process variables. Values of process
variables can be seen in parameters 0134
in the ACS-PAN output display. Value is calculated by taking given parameter from the operating
data group (Group 1), and multiplying and dividing it with given coefficients. The unit and number of
decimal digits is configurable.
See example below.
Code Description
3401 DISPLAY SEL
Selects displayed variables for the output display of
the ACS-PAN control panel.
1 =
STANDARD
Panel displays standard variables.
2 =
PROCESS VAR
Panel displays process variables. See Figure 42.
3402 P VAR 1 SEL
Selection of process variable 1. Number of any parameter of the group 1
3403 P VAR 1 MULTIP
Process variable 1 multiplier.
3404 P VAR 1 DIVISOR
Process variable 1 divider.
3405 P VAR 1 SCALING
Decimal point location of process variable 1, when
displayed. Refer to Figure 43.
3406 P VAR 1 UNIT
Process variable unit.
0 =
4 = %
NOT SEL
1 = A
5 = s
2 = V
6 = h
3 = Hz
7 = rpm
104
PROCESS VAR
8 = kh
12 = mV
9 = °C
13 = kW
10 = lb ft
14 = W
11 = mA
15 = kWh
http://nicontrols.com
1 and 0135
PROCESS VAR
Process variable 1
0.0A
OUTPUT
Figure 42 ACS-PAN output display when
process variable display is selected.
OPERATING DATA
Value
0
1
2
3
Figure 43 Display with different decimal point
locations when calculated value is 125.
3
16 = °F
20 = m
/h
3
17 = hp
21 = dm
/s 25 = PSI
18 = MWh
22 = bar
19 = m/s
23 = kPa
2
optionally
AND
Frequency reference
50.0 Hz
0.0 Hz
Process variable 2
.
Display
125
12.5
1.25
0.125
24 = GPM
28 = MGD
29 = inHg
26 = CFM
30 = FPM
27 = ft
31 = Cst
ACS 400 User's Manual