ABB ACS 400 User Manual page 61

Ac drives for speed control
Hide thumbs Also See for ACS 400:
Table of Contents

Advertisement

Code Name
9908 MOTOR NOM SPEED
Nominal motor speed from motor name plate.
Range 0 - 3600 rpm
Default: 1750 rpm
9909 MOTOR NOM POWER
Nominal motor power from name plate.
Range: 0.1 - 134.1 HP
Default: 3.0 - 50.0 HP depending on the type of the frequency converter
9910 MOTOR COS PHI (
Nominal motor cos phi from name plate.
Range: 0.50 - 0.99
Default: 0.83
Group 01
OPERATING DATA
0128 LAST FAULT
Last recorded fault (0 = no fault). See "Diagnostics" on page 35.
Can be cleared with the control panel by pressing the UP and DOWN buttons
simultaneously while in parameter set mode.
Group 10
COMMAND INPUTS
1003 DIRECTION
Rotation direction lock.
1 =
FORWARD
2 =
REVERSE
3 =
REQUEST
If you select
REQUEST
Default: 3 (
REQUEST
Group 11
REFERENCE SELECT
1105
EXT REF1 MAX
Maximum frequency reference in Hz.
Range: 0 - 250 Hz
Default value: 60 Hz or 62 Hz depending on the selected application macro.
Group 12
CONSTANT SPEEDS
1202 CONST SPEED 1
Range for all constant speeds: 0 - 250.0 Hz
Default value: 5.0 Hz
1203 CONST SPEED 2
Default value: 10.0 Hz
1204 CONST SPEED 3
Default value: 15.0 Hz
50
)
POWER FACTOR
, the direction is set according to the given direction command.
) or 1 (
) depending on the selected application macro.
FORWARD
http://nicontrols.com
User
ACS 400 User's Manual
S