Application Macro ABB Standard

This general purpose macro is typical 2-wire I/O configuration. It gives two more preset speeds
compared to Factory Macro (0).
The value of parameter 9902 is 1 (
Input signals
• Start, stop and direction
(DI1,2)
• Analog reference (AI1)
• Preset speed selection (DI3,4)
• Ramp pair 1/2 selection (DI5)
*Constant speed selection: 0 = open, 1 = connected
ABB Standard parameter values:
1001
1
EXT
1002
2
EXT
1003
DIRECTION
1102
1/
EXT
1103
EXT REF
1105
EXT REF
1106
EXT REF
1201
CONST SPEED SEL
1401
RELAY OUTPUT
56
ABB STANDARD
Output signals
DI3
0
1
0
1
2 (
COMMANDS
0 (
COMMANDS
3 (
2
6 (
EXT
SEL
1
1 (
SELECT
1
60 Hz
MAX
2
0 (
SELECT
7 (
1
3 (
http://nicontrols.com
).
• An. output AO: Frequency
• Relay output 1: Fault
• Relay output 2: Running
External Reference 1: 0...10 V <=> 0...50 Hz
Reference voltage 10 VDC
Not used
Output frequency 0...20 mA <=> 0...50 Hz
+24 VDC
Start/Stop: Activate to start
Fwd/Rev: Activate to reverse rotation direction
Constant speed selection*
Constant speed selection*
Ramp pair selection. Activate to select ramp pair 2.
Relay output 1, programmable
Default operation: Fault => 17 connected to 18
Relay output 2, programmable
Default operation: Running => 20 connected to 22
DI4
Output
0
Reference through AI1
0
Const speed 1 (1202)
1
Const speed 2 (1203)
1
Const speed 3 (1204)
1,2)
1402
DI
RELAY OUTPUT
)
1503
NOT SEL
AO CONTENT MAX
)
1601
REQUEST
RUN ENABLE
1)
1604
EXT
FAULT RESET SEL
1)
2008
AI
MAXIMUM FREQ
2105
PREMAGN SEL
)
2201
KEYPAD
ACC
3,4)
4001
DI
PID GAIN
(-1))
4002
FAULT
PID INTEG TIME
Jumper Setting
2
2 (
RUN
60 Hz
0 (
NOT SEL
0 (
KEYPAD
60 Hz
0 (
NOT SEL
/
1/2
5 (DI5)
DEC
SEL
1.0
60 s
ACS 400 User's Manual
)
)
)
)