ABB ACS 400 User Manual page 49

Ac drives for speed control
Hide thumbs Also See for ACS 400:
Table of Contents

Advertisement

Table 6 Faults.
Fault Code
1
OVERCURRENT
2
DC OVERVOLTAGE
3
400
ACS
4 **
SHORT CIRCUIT
5
OUTPUT OVERLOAD
6
DC UNDERVOLTAGE
7
ANALOGUE INPUT
8
ANALOGUE INPUT
9
MOTOR OVERTEMP
10
PANEL LOSS
11
PARAMETERING
12
MOTOR STALL
13
SERIAL COMM LOSS
14
EXTERNAL FAULT SIGNAL
15 **
OUTPUT EARTH FAULT
38
Display
Description
Output current is excessive.
Intermediate circuit DC voltage is excessive.
ACS 400 heat sink temperature is excessive. Temperature trip limit is
OVERTEMP
95 °C.
Fault current. Possible reasons for this fault are:
Inverter overload condition. The ACS 400 output current exceeds the
ratings given in "Specifications" on page 21 of this manual.
Intermediate circuit DC voltage is not sufficient.
1
Analog input 1 loss. Analog input value is less than
See also parameter 3001
2
Analog input 2 loss. Analog input value is less than
See also parameter 3001
Motor overtemperature condition as estimated by the ACS 400. Refer
to parameters 3004 – 3008.
Panel communication loss. Control panel is disconnected when the
drive is receiving start, stop and direction commands from the panel.
- Drive is in local control mode (LOC is shown in the control panel
display), or
- Drive is in remote control mode (REM is shown) and is programmed to
accept start/stop, direction or reference from the panel. Refer to
parameters in groups 10 COMMAND INPUTS and 11 REFERENCE
SELECT.
See also parameter 3002
Parameter values are inconsistent:
Motor stall. This may be caused by excessive load or insufficient motor
power. Refer to parameters 3009 – 3012.
Serial communication through Standard Modbus Channel is lost.
External fault is active. See parameter 3003
Ground fault. The load on the input power system is out of balance.
http://nicontrols.com
Motor load may be too high
Acceleration time may be too short (parameters 2201
1 and 2203
TIME
ACCELER TIME
Motor or motor cable is faulty or connected wrong.
Check the input power supply for static or transient overvoltages
Deceleration time may be too short (parameters 2202
1 and 2204
TIME
DECELER TIME
Brake chopper (if present) may be underdimensioned
Check air flow and fan operation.
Check motor power against unit power.
There is a short-circuit in the motor cable(s) or motor
Supply disturbances
Input power supply phase may be missing
Fuse may be blown
<
AI
<
AI
PANEL LOSS
1 >
MINIMUM AI
MAXIMUM AI
2 >
MINIMUM AI
MAXIMUM AI
>
MINIMUM FREQ
MAXIMUM FREQ
PFC block tries to use the I/O extension module (NDIO) but the
DDCS link is not programmed properly
Check connections between external control system and the
ACS 400.
Refer to parameters 5003
.
FUNC
There may be a fault in the motor or motor cable.
Motor cable may be too long.
2).
2)
MINIMUM AI
.
MIN FUNCTION
MINIMUM AI
.
MIN FUNCTION
.
1 (parameters 1301, 1302)
2 (parameters 1304, 1305)
(parameters 2007, 2008)
and 5004
COMM FAULT TIME
EXTERNAL FAULT
ACS 400 User's Manual
ACCELER
DECELER
1 (1301).
2 (1306).
COMM FAULT
.