K Control Terminals
Main I/O terminal X1
.
X1 Identification
1
SCR
Terminal for signal cable screen. (Connected internally to chassis ground.)
2
AI 1
Analog input channel 1, programmable.
Default: 0 - 10 V (R
0 - 20 mA (R
Resolution 0.1 % accuracy ±1 %.
3
AGND
Analog input circuit common. (Connected internally to chassis ground through 1 MΩ.)
4
10 V
10 V/10 mA reference voltage output for analog input potentiometer, accuracy ±2 %.
5
AI 2
Analog input channel 2, programmable.
Default: 0 - 20 mA (R
0 - 10 V (R
Resolution 0.1 % accuracy ±1 %.
6
AGND
Analog input circuit common. (Connected internally to chassis ground through 1 MΩ.)
Analog output, programmable. Default: 0-20 mA (load < 500 Ω) <=>0-f
7
AO1
8
AGND
Common for DI return signals.
9
24 V
Auxiliary voltage output 24 V DC / 250 mA (reference to AGND).
Short circuit protected.
10 DCOM1
Digital input common for DI1, DI2 and DI3.
To activate a digital input, there must be ≥+10 V (or ≤-10 V) between that input and
DI Configuration
DCOM1. The 24 V may be provided by the ACS 400 (X1:9) using the connection examples
(see Section M) or by an external 12-24 V source of either polarity.
HVAC Hand-Auto Macro (8) (default)
11 DI 1
AUTO mode Start/Stop Close to start. Motor
will ramp up to frequency reference. Open to
stop. Motor will coast to stop.
12 DI 2
Run Enable: Close to enable
13 DI 3
Select constant speeds 1 to 7
14 DI 4
Select constant speeds 1 to 7
15 DI 5
Select constant speeds 1 to 7
16 DCOM2
DCOM2 digital input common for DI4, DI5
17 RO1
18 RO1
19 RO1
20 RO2
21 RO2
22 RO2
Digital input impedance 1.5 k
Use multi-strand 0.5-1.5 mm
Note! For safety reasons the fault relay signals a "fault" when the ACS 400 is powered
down.
Note! DI 4 and 5 are electrically isolated from DI1, 2, and 3. To utilize DI4 and 5, a jumper
must be connected. See section M for details.
Note! Terminals 3, 6 and 8 are at the same potential.
ACS 400 User's Manual
= 200 kΩ) (J1:AI1 open) <=> 0 - f
i
= 500 Ω) (J1:AI1 closed) <=> 0 - f
i
= 500 Ω) (J1:AI2 closed) <=> 0 - f
i
= 200 kΩ) (J1:AI2 open) <=> 0 - f
i
Relay output 1, programmable (default: fault => 17 connected to 18).
Relay output 2, programmable (default: running => 20 connected to 22).
.
2
(20-16 AWG) wire.
http://nicontrols.com
Description
frequency reference
nom
frequency reference
nom
frequency reference
nom
frequency reference
nom
12 - 250 V AC / 30 V DC, 10 mA - 2 A
12 - 250 V AC / 30 V DC, 10 mA - 2 A
output frequency
nom
15