Code Description
1607 PARAM. SAVE
Parameter save function. Selection 1 (
(
) is displayed when all parameter are saved.
DONE
When parameters are altered through Standard Modbus or DDCS channels, altered values are not
automatically saved to permanent memory. Instead, this parameter must be used.
0 =
DONE
1 =
...
SAVE
Note! Parameter modifications done from the control panel are normally stored immediately to permanent
memory. However, if 1602 PARAMETER LOCK is set to 2 (
panel are saved only if this parameter 1607 is used.
1608 DISPLAY ALARMS
Controls the visibility of some of the alarms, see "Diagnostics" on page 35.
1 =
NO
Some of the alarms are suppressed.
2 =
YES
All of the alarms are enabled.
ACS 400 User's Manual
...) saves all altered parameters to permanent memory. Value 0
SAVE
http://nicontrols.com
), modifications done from the control
NOT SAVED
87