ABB ACS 400 User Manual page 133

Ac drives for speed control
Hide thumbs Also See for ACS 400:
Table of Contents

Advertisement

Code Description
8119 AUTOCHNG LEVEL
Sets the operation limit for the Autochange logic. This parameter can be used to deny Autochange when the
Pump-Fan system is operating near maximum capacity. When the output from the PID/PFC control block
exceeds the level set by this parameter, Autochange operation is not possible.
Figure 51 Autochange level.
Autochange operation
The purpose of the Autochange operation is to ensure equal duty time for all the motors. Each motor in the
system will in its turn be connected to the ACS 400 as well as direct on line. The starting order of the motors
is changed when Autochange is done.
To use the Autochange function, an external alternation switchgear is needed. Refer to "Appendix B" on
page 157 for more information. When Autochange is used, the interlocks (parameter 8120) must also be
taken into use.
The Autochange is performed when the Autochange Interval (parameter 8118) is elapsed from the previous
autochange and the output from the PFC is below the level set by this parameter.
Autochange operation is as follows:
1. The speed controlled motor stops. The contactor of the speed controlled motor is switched off.
2. The starting order is changed (the starting order counter steps onward).
3. The contactor of the motor that will be the new speed controlled motor is switched off (if the motor is
running). If other motors are running, they will not be interrupted.
4. The contactor of the new speed controlled motor is switched on. The autochange switchgear connects
this motor to the ACS 400.
5. Time set with parameter 8122
6. Speed controlled motor starts. If a constant speed motor was stopped in Step 3, one more motor is
connected direct on-line by switching on the contactor of that motor. After this step the same number of
motors is running as before the Autochange.
7. Normal PFC operation continues.
As an example, the starting order in a three motor system is changed as follows:
First start: Motor no. 1, motor no. 2, motor no. 3.
Second start: Motor no. 2, motor no. 3, motor no. 1.
Third start: Motor no. 3, motor no. 1, motor no. 2. (etc...)
If some motors in the system are interlocked, the Autochange logic skips them. If all interlocks are active
and no motor can be started, an interlock alarm (Alarm 30) is displayed.
Note! The ACS 400 always coasts to stop when autochange is performed.
Note! Autochange can also occur during PID sleep.
Note! When the ACS 400's power supply is switched off, the values of the starting order counter and
Autochange Interval counter are stored in the permanent memory. The counters continue from the stored
values after the power supply is switched on again.
122
Output frequency
f
MAX
No aux
motors
Allowed autochange area
8119
PFC START DELAY
http://nicontrols.com
1 aux
2 aux
motor
motors
100 %
AUTOCHNG LEVEL
is waited.
PID output
ACS 400 User's Manual

Advertisement

Table of Contents
loading

Table of Contents