Section 2 Functional Description
Bit
Value
7
0x00000080 No
During the update of status information for a modular DeviceNet adapter, the I/O
modules configured under the adapter (the child units) are also updated with the
same status information. The Sub I/O modules that are configured with addresses
1 to 63 under the adapter are updated with status information.

Status Handling for EtherNet/IP Device

Table 8
and ExtendedStatus.
Bit
Value
13
0x00002000 Connection
Error
14
0x00004000 Configuration
Error
31
0x80000000 Device Not
Found
9ARD000014-600 A
Table 7. Extended status of DeviceNet Device
Text
Indication
Warning
Connection
Enabled
shows all EtherNet/IP device specific Unit Status bits in ErrorAndWarnings
Table 8. Errors and Warnings of EtherNet/IP device
Text
Indication
Error
Error
Error
Status Handling for EtherNet/IP Device
Alarm/Event
Severity
Alarm
Low
Alarm/Event
Severity
Alarm
High
Alarm
High
Alarm
High
Description
Set when no
connections are
enabled for the device
Description
Set when connection
request from CI873
to this device returns
error.
Set when the CI
receives wrong
response when it
wrote configuration
data.
Set when the Device
is not present in the
network
39