Section 4 Configuration
Channel Name
Ctrl Out 0
Bits 06-08 Calibration Control bits - bits 06. 07 and 08
Bits 09-10 10
Bits 11-12 12
Bit 13
9ARD000014-600 A
Table 27. Description of Channels for 200-IP2 (Continued)
Bit
06
Enable bit - When this bit is set (1), the counter can be
calibrated
07
Direction bit - When this bit is set (1), calibration is
performed in a negative direction; when reset (0),
calibration is performed in a positive direction.
08
Reset bit - Calibration is acknowledged and a new
calibration is enabled on a positive edge on this bit.
09
0
0
0
1
1
0
1
1
11
0
0
0
1
1
0
1
1
Rollover bit - When set (1), the counter counts up to the preset
and then restarts at 0. If this bit is reset (0) (not rollover), the
rollover preset value = FFFF (hex = 65535 (decimal).
Definition
Gate Control bits
No gate function on input G
Counting only if G is high (active)
Counting only if G is low (inactive)
The counter can be calibrated when G is high
(active)
Store Control bits - These bits will trigger a Store
only if the channel Store status bit (L0 or L1) is
cleared (0).
Save the counter value on the positive edge of Z (if
StoredX= O)
Save the counter value on the positive edge of G (if
StoredX= O)
Save the counter value on the negative edge of G (if
StoredX= O)
Save the counter value on the positive edge and
negative edge of G (if Stored X = 0)
Configuring S200 I/O Modules
157