ABB AC 800M Configuration page 226

Hide thumbs Also See for AC 800M:
Table of Contents

Advertisement

Sl
Message
No
9
IO files can be
imported only along
with corresponding
adapter files!
10
The wizard cannot
proceed as the file
is not as per CIP
specifications.
There are required
fields in the File
section that are
missing. Please
restart the wizard
with the correct
EDS file.
11
The wizard cannot
proceed as the file
is not as per CIP
specifications.
There are required
fields in the
Device section that
are missing. Please
restart the wizard
with the correct
EDS file.
226
Table 41. Messages - Import of EDS Files (Continued)
Reason
Import has been
started with IO EDS
file instead of
adapter EDS file in
case of Modular IO
Any of the
mandatory fields in
File Section
required in EDS file
is missing or fields
available as not as
per CIP
specifications
(example: create
date, create time
etc.)
Any of the
mandatory fields in
Device Section
required in EDS file
is missing or fields
available as not as
per CIP
specifications
(example: vendor
code, product code
etc.)
Appendix A Troubleshooting EDS File
Applicability
Based on Device
Classification
Import will abort. 
Modular
EtherNet/IP/
Start the import with
DeviceNet
an adapter EDS file in
case of Modular IO.
Import will abort. 
EtherNet/IP/
DeviceNet
Contact the vendor to
get device EDS files
with all the mandatory
fields.
Import will abort. 
EtherNet/IP/
DeviceNet
Contact the vendor to
get device EDS files
with all the mandatory
fields.
Additional
Information and
Workaround
9ARD000014-600 A