Section 4 Configuration
Parameter
Default Value
Conn Poll
Depends on the
InputSize
device support
as stated in its
EDS file
Conn Poll
Depends on the
OutputSize
device support
as stated in its
EDS file
COS Connection
The Change Of State (COS) Connection parameters in the hardware editor are
described in
between LD 800DN and all DeviceNet slaves configured under it stops
momentarily.
Default
Parameter
Value
Acknowledge
16 ms
time
Heart Beat
250 ms
9ARD000014-600 A
Table 19. Poll Connection Parameters
Read
Data
Only /
Type
Editable
Int
Read
Only
Int
Read
Only
Table
20. Upon modification of the editable parameters, the connection
Table 20. COS Connection Parameters
Read Only/
Type
Editable
Dint
Editable
Int
Editable
Communication Related Parameters
Number of bytes of data that gets
transferred from the device to the linking
device over the Poll connection.
Number of bytes of data that gets
transferred from linking device to the device
over the Poll connection.
Description
It is the amount of time that a producing node
(for example - DeviceNet slave) waits for an
acknowledgement (ACK) from the consuming
node (linking device LD 800DN) before it re-sends
the data.
It is the background production interval for the
change-of-state connection. It is the rate at which
the device produces the data, even if the data has
not changed.
Description
127