Configuration
Configuration
This section describes the configuration of the LD 800DN Ethernet to DeviceNet
linking device.
BridgeWay Configuration Tool
Before configuring the LD 800DN in the Control Builder and going online, it should
be configured with an IP Address and MAC ID. This is done by using the
BridgeWay Configuration tool.
The BridgeWay Configuration is a Microsoft Windows application that
communicates with the LD 800DN over a standard RS-232 serial link, using the PC
serial port or USB serial adapter.
The BridgeWay Configuration must be used only for setting the IP address, MAC
ID and upgrading the firmware. Making any other changes will cause a conflict
with the settings downloaded from CI873.
Installing BridgeWay Configuration Tool
To install BridgeWay Configuration from the System 800xA Media, run Setup.exe
available in the following directory of the System 800xA Media:
•
•
Connecting to the LD 800DN Module
Connect the system, in which BridgeWay Configuration is run, to the LD 800DN
module by using a standard Null-Modem (pin 2 and pin 3) serial cable. This cable
should connect the PC serial port (or the USB serial adapter, if used) to the 9 pin D-
Sub connector on the module.
BridgeWay Configuration scans for each available port, detects the connection and
automatically sets the baud rate.
174
For Control Builder Professional:
\Engineering & Development\Control Builder M\Tools\
LD800DN\ConfigurationTool
For Compact Control Builder:
\Tools\ABB\LD800DN\ConfigurationTool.
Section 6 Linking Device LD 800DN
9ARD000014-600 A