ABB AC 800M Configuration page 159

Hide thumbs Also See for AC 800M:
Table of Contents

Advertisement

Section 4 Configuration
Channel Name
Ctrl Out 1
Bits 06-08 Calibration Control bits - bits 06, 07 and 08
Bits 09-10 10
Bits 11-12 12
Bit 13
9ARD000014-600 A
Table 27. Description of Channels for 200-IP2 (Continued)
Bit
06
Enable bit - When this bit is set (1), the counter can be
calibrated.
07
Direction bit - When this bit set (1), calibration is
performed in a negative direction; when reset (0),
calibration is performed in a positive direction.
08
Reset bit - Calibration is acknowledged and a new
calibration is enabled on a positive edge on this bit.
09
0
0
0
1
1
0
1
1
11
0
0
0
1
1
0
1
1
Rollover bit - When set (1), the counter counts up to the preset
and then restarts at 0. If this bit is reset (0) (not rollover), the
rollover preset value = FFFF (hex = 65535 (decimal).
Definition
Gate Control bits
No gate function on input G
Counting on y if G is high (active)
Counting on y if G is low (inactive)
Calibration if G is high {active) and ???
Store Control bits - These bits will trigger a Store
only if the channel Store status bit (LO or L1) is
cleared (O).
Save the counter value on the positive edge of Z (if
Store X= O)
Save the counter value on the positive edge of G (if
Store X= O)
Save the counter value on the negative edge of G (if
Store X= O)
Save the counter value on the positive edge and
negative edge of G (if Store X= O)
Configuring S200 I/O Modules
159

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents