Configuring EtherNet/IP Device
Parameter Data Type Unit
Class
Dint
1 Exclusive
Owner
T2ORPI
Class
Enum
1 Exclusive
Owner
Enabled
(1) If the IP Address parameter is left blank, then it is evaluated from the EtherNet/IP device's position in the hardware
tree along with the IP address of its CI873 parent unit. The first three octets are taken from the parent unit and last
octet from the hardware tree position.
140
Table 23. Settings for EtherNet/IP Device Unit (Continued)
Min
ms
10
-
-
Editable
Max
/Read
Only
500
Editable
Requested Packet Interval in
milliseconds for T->O packets.
Upon modification, connection with
the Ethernet/IP device is re-
established.
-
Editable
Class 1 connection is logical segment
that is connection point based.
The name of the connection is
derived from Connection Manager
section of EDS file by the EDS DIW.
Options are:
Section 4 Configuration
Description
Enabled - New connection will
be established and the data
starts updating on the
corresponding connection
channel.
Disabled - Connection that is
already established, will be
closed.
9ARD000014-600 A