Configuring LD 800DN Linking Device Unit
Table 17. Settings for LD 800DN Linking Device Unit (Continued)
Parameter Data Type Unit
Electronic
Enum
Key Major
Revision
IP
String
(1)
Address
114
Min
Max
0
2
-
-
-
Editable
/Read
Only
Editable
Criteria that can be specified by user
for LD 800DN to accept connection
from CI873 only when major revision
of LD 800DN configured in Control
Builder matches or is greater than the
major revision of LD 800DN device in
the network.
Values are:
Disable Keying, Exact Match,
Current and Higher
Upon modification, connection
between LD 800DN and CI873 gets
disconnected and connected again.
Hence communication with
DeviceNet slaves stop momentarily
Editable
The IP address of the linking device
LD 800DN in the network. It must be
an IP address on the same subnet as
where the CI873 is placed.
If the IP address is blank, then first
three fields are taken from its parent
CI873 IP address and the fourth is
taken from its hardware tree position.
Upon modification, connection of
CI873 with the Linking Device is
reestablished.
Section 4 Configuration
Description
9ARD000014-600 A