ABB AC 800M Configuration page 139

Hide thumbs Also See for AC 800M:
Table of Contents

Advertisement

Section 4 Configuration
Table 23. Settings for EtherNet/IP Device Unit (Continued)
Parameter Data Type Unit
Electronic
Enum
Key Major
Revision
IP
String
(1)
Address
Class
Dint
1ExclusiveO
wner
O2TRPI
9ARD000014-600 A
Min
Max
0
2
-
-
-
ms
10
500
Configuring EtherNet/IP Device
Editable
/Read
Only
Editable
Criteria that can be specified by user
for EtherNet/IP to accept connection
from CI873 only when major revision
of EtherNet/IP configured in Control
Builder matches or is greater than the
major revision of EtherNet/IP device
in the network.
Values are:
Disable Keying, Exact Match, Current
and Higher
Upon modification, connection
between EtherNet/IP and CI873 gets
disconnected and connected again.
Editable
The IP address of the EtherNet/IP
device on the network. It must be an
IP address on the same subnet as
where the CI873 is placed.
If the IP address is blank, then first
three fields are taken from its parent
CI873 IP address and the fourth is
taken from its hardware tree position.
Upon modification, connection of
CI873 with the EtherNet/IP Device is
re-established.
Editable
Requested Packet Interval in
milliseconds for O->T packets.
Upon modification, connection with
the Ethernet/IP device is re-
established.
Description
139