IP Address and MAC ID Configuration for LD 800DN
The DIP Switch value is the binary value of the last byte in the 4 byte IP address.
Considering it as n, then:
A non-zero DIP switch setting overrides any other IP Address setting done.
Hence, set the DIP switch value to zero if other methods are used to set the IP
address of the LD 800DN.
Refer to
Figure 67. DIP Switch Configuration
The switches are set to 00010100 (20 decimal) (The switch position is shown in
White in
The numbers on the switches of DIP switch do not correspond to bit locations in
the address value. Instead, the numbers are reversed. That is, bit 0 is set by
switch 8.
Setting the IP Address through the Web Page
The IP address of the linking device can also be configured by using the LD 800DN
Status & Settings web page from the linking device.
To view the web page, use http://<IP Address> as the URL, where
<IP Address> is the current IP Address of the module. This URL brings up the
Status & Settings web page. For details on the Status & Settings web page and on
setting up the IP address, refer
180
IP Address – 192.168.1.n
Subnet Mask – 255.255.255.0
Gateway Address – 0.0.0.0 (No gateway set)
Figure
67, for a sample illustration of a DIP Switch.
Figure
67). Hence, the IP address of the module is set to 192.168.1.20.
Section 6 Linking Device LD 800DN
Status & Settings Web Page
on page 196.
9ARD000014-600 A