Configuring LD 800DN Linking Device Unit
Table 17. Settings for LD 800DN Linking Device Unit (Continued)
Parameter Data Type Unit
I/O
Dint
Connection-
O -> T RPI
I/O
Dint
Connection
- T -> O RPI
118
Min
Max
ms
10
500
ms
10
500
Editable
/Read
Only
Editable
Requested Packet Interval in
milliseconds for O -> T packets. The
value is used to allocate bandwidth at
each of the producing nodes (CI873)
CI873 re-establishes the connection
with the Linking Device. The
bandwidth is allotted to the new value
by the CI873. The default value is
10ms.
Upon modification, communication of
CI873 with all DeviceNet devices is
stopped till the connection is re-
established.
Editable
Requested Packet Interval in
milliseconds for T -> O packets
Measures how frequently CI873
requires the transmission of data
from the linking device. The default
value is 10ms.
Upon modification, CI873
re-establishes the connection with
linking device. Communication of
CI873 with all DeviceNet devices is
stopped till the connection is 
re-established.
Section 4 Configuration
Description
9ARD000014-600 A