10.4

Online Module Change Procedure

This section and the following sections describe two online module change procedures: setting parameters using the
configuration function and setting parameters using a sequence program. The same procedures are applied to GX
Developer.
• When using GX Works2
Range setting
Factory default range
User range
• When using GX Developer
Range setting
Factory default range
User range
*1
"Another system" is a programmable controller system which does not have the CT input module to be replaced, and is
composed of modules such as a power supply module and a CPU module. "Another system" has power supply which
can be turned on and off and modules which can be removed and mounted.
(1) System configuration
The following system configuration is used to explain the online module change procedure.
(a) Without another system
(b) With another system
CT input module (X/Y0 to X/YF)
Parameter setting
Configuration function
Sequence program
Configuration function
Sequence program
CPU module
CT input module (X/Y0 to X/YF)
CPU module
CHAPTER 10 ONLINE MODULE CHANGE
*1
Another system
Present
Absent
Present
Absent
*1
Another system
Present
Absent
Other system
Reference
Page 185, Section 10.5
Page 190, Section 10.6
Page 196, Section 10.7
Page 207, Section 10.9
Page 201, Section 10.8
Page 213, Section 10.10
Reference
Page 190, Section 10.6
Page 201, Section 10.8
Page 213, Section 10.10
CPU module
10
183