Mitsubishi Electric MELSEC-Q series User Manual page 30

Programmable controller current transformer input module
Hide thumbs Also See for MELSEC-Q series:
Table of Contents

Advertisement

● Use the CT input module so that the input and output are within the specified practical ranges. If a value is out of the
range, the maximum resolution and accuracy may not fall within the range described in performance specifications.
(Avoid values on the dotted line region in the graph of I/O conversion characteristics.)
● For each input range, avoid inputting a value that exceeds the one in the following table to the CT. (Avoid inputting the
value that is 150% or more over the maximum input range.) Elements may be damaged.
Input range setting
0 to 5AAC
0 to 50AAC
0 to 100AAC
0 to 200AAC
0 to 400AAC
0 to 600AAC
28
CT input value (primary current value of a CT)
7.5A or more
75A or more
150A or more
300A or more
600A or more
900A or more

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents