(3) Primary delay filter
Depending on the set time constant, digital output values with smoothed noise can be obtained. A smoothing
degree varies by setting the time constant.
The following are the relational expressions of time constants and digital output values.
*1
[n = 1]
Y
= 0
n
[n = 2]
Y
= y
+
n
n-1
[n  3]
Y
= Y
+
n
n-1
Y
: Present digital output value
n
Y
: Last digital output value
n-1
Number of sampling
n
:
processing
TA
: Time constant
*1
When n is 2 or larger, Conversion completed (1) is stored in Conversion completed flag (Un\G10).
*2
Set a value which is equal to or larger than the sampling cycle. If the time constant is smaller than the sampling cycle,
the error (error code: 32) occurs, and the digital output value becomes 0.
t
(y
- y
)
n
n-1
t + TA
t
(y
- Y
)
n
n-1
t + TA
y
: Digital output value before smoothing
n
y
: Last digital output value before smoothing
n-1
t
: Sampling cycle
*2
(ms)