Mitsubishi Electric MELSEC-Q series User Manual page 196

Programmable controller current transformer input module
Hide thumbs Also See for MELSEC-Q series:
Table of Contents

Advertisement

(From the previous page)
194
6.
Set Conversion enable/disable setting (Un\G0) to
Enable (0) for the channel used.
7.
Turn on Operating condition setting request (Y9).
8.
Check that Operating condition setting completed
flag (X9) turns off, then turn off Operating condition
setting request (Y9).
9.
Monitor CH Digital output value (Un\G11 to
Un\G18) to check if the digital conversion is
performed properly.
10.
Before starting the control, check the CT input
module for the following. If an error occurs, refer to
TROUBLESHOOTING (
and take a corrective action.
• If the RUN LED is on.
• If the ERR. LED is off.
• If Error flag (XF) is off.
11.
Since the new module is in the default status, initial
settings must be configured using a sequence
program after the control resumed. Before
configuring the initial settings, check that the initial
setting program is proper, satisfying the following.
Normal system configuration
• Create a sequence program that sets the initial
settings when Module READY (X0) of the CT input
module turns on.
• Do not create a sequence program which sets the
initial settings for only one scan after RUN. In this
case, the initial settings are not set.
When used on remote I/O network
• Insert a user device where the initial setting will be
set at any timing (initial setting request signal) into the
sequence program.
• Do not create a sequence program which sets the
initial setting only one scan after a data link start of
the remote I/O network. In this case, the initial setting
is not set.
Page 221, CHAPTER 11)