When Operating condition setting completed flag (X9) is off, the digital conversion processing is not executed.
Operating condition setting completed flag (X9) turns off in the following status.
• When Operating condition setting request (Y9) is on
Module READY (X0)
Operating condition setting
completed flag (X9)
Operating condition setting
request (Y9)
Conversion completed
flag (XE)
(7) Offset/gain setting mode flag (XA)
(a) Offset/gain setting mode
When registering the value which was adjusted with the offset/gain setting to the module, use Offset/gain
setting mode flag (XA) as an interlock condition to turn on then off User range write request (YA).
For the offset/gain setting, refer to the following.
• Offset/gain Setting (
Module READY (X0)
Offset/gain setting mode
flag (XA)
User range write request (YA)
(b) Normal mode
At the user range setting restoration, use Offset/gain setting mode flag (XA) as an interlock condition to turn on
then off User range write request (YA).
For the user range setting restoration, refer to the following.
• ONLINE MODULE CHANGE (
Module READY (X0)
Offset/gain setting mode flag (XA)
User range write request (YA)
CHAPTER 5 I/O SIGNALS ASSIGNED TO THE CPU MODULE
Controlled by the CT input module
Controlled by the sequence program
ON
ON
OFF
ON
OFF
ON
OFF
Page 148, Section 8.5)
Controlled by the CT input module
Controlled by the sequence program
OFF
ON
OFF
Page 180, CHAPTER 10)
Controlled by the CT input module
Controlled by the sequence program
ON
OFF
OFF
ON
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
ON
ON
OFF
OFF
83
5