(2) Error code list
If the following errors occur on the CT input module while data is written to or read from the CPU module, the
corresponding error code below is stored in Latest error code (Un\G19).
The error is reported to the CPU module also.
Error code
(decimal)
CH Input range setting (Un\G150 to Un\G157) is set to a
value outside the range of 0000
*1
10
The channel where the error has occurred fits in .
111
A hardware failure has occurred on the module.
A value other than 0 is set to Switch 5 on the intelligent function
112
module switch setting.
*1
The backup data has a problem.
113
*1
The writing of backup data went wrong.
114
Since Conversion enable/disable setting (Un\G0) has a channel
*1
115
of conversion enable, the backup data cannot be written.
Since Conversion enable/disable setting (Un\G0) has a channel
*1
of conversion enable, the values of buffer memories cannot be
116
restored to default settings.
An invalid value is set to the offset/gain setting.
*1
120
The channel where the error has occurred cannot be identified.
An invalid value is set to offset/gain setting.
*1
12
The channel where the error has occurred fits in .
The G(P).OGSTOR instruction was executed in the offset/gain
*2
161
setting mode.
• The G(P).OGSTOR instruction has been consecutively
executed.
*1
• For the offset/gain setting, a setting value has been
162
consecutively written to the non-volatile memory more than
25 times.
224
Description and the error cause
to 0005
H
H
Set CH Input range setting (Un\G150 to Un\G157)
to a value within the range of 0000
or 0010
to 0015
.
H
H
0010
H
Turn the power off then on.
If the error occurs again, a failure might have occurred
on the module. Please consult your local Mitsubishi
system service, service center, or representative,
explaining a detailed description of the problem.
Set 0 to Switch 5 on the intelligent function module
switch setting in the parameter setting.
Check the digital output value.
If there is a problem of the digital output value, please
consult your local Mitsubishi system service, service
center, or representative, explaining a detailed
description of the problem.
Write the backup data.
If the error occurs again, a failure might have occurred
on the module. Please consult your local Mitsubishi
system service, service center, or representative,
explaining a detailed description of the problem.
Set Conversion enable/disable setting (Un\G0) to
Disable (1) for all channels, then write the backup
data.
Set Conversion enable/disable setting (Un\G0) to
Disable (1) for all channels, then execute the default
setting registration function.
Start over the offset/gain setting of all channels where
the user range setting is used.
If the error occurs again, a failure might have occurred
on the module. Please consult your local Mitsubishi
system service, service center, or representative,
explaining a detailed description of the problem.
Start over the offset/gain setting of the channel where
the error has occurred.
If the error occurs again, a failure might have occurred
on the module. Please consult your local Mitsubishi
system service, service center, or representative,
explaining a detailed description of the problem.
Do not execute the G(P).OGSTOR instruction in the
offset/gain setting mode.
• Execute the G(P).OGSTOR instruction only once
per module.
• Write the setting value into the non-volatile memory
only once for each offset/gain setting.
Action
H
to 0015
.
H
to 0005
or
H

Hide quick links: