(20)CH Input range setting (Un\G150 to Un\G157)
Set the CT input range for each channel.
For details on the input range setting, refer to the following.
• Input Range Setting (
Factory default range
User range
• In the channel where a setting value other than the above is set, an error occurs. The error code (10) is
stored in Latest error code (Un\G19) and Error flag (XF) turns on. The setting range before the error occurs
is applied.
(a) Enabling the setting
Turn on then off Operating condition setting request (Y9) to enable the setting.
(b) Default value
All channels are set to 0 to 5AAC (factory default range) (0000
Since 0 to 5AAC (factory default range) (0000
CT.
Page 34, Section 4.2)
Input range
0 to 5AAC
0 to 50AAC
0 to 100AAC
0 to 200AAC
0 to 400AAC
0 to 600AAC
0 to 5AAC
0 to 50AAC
0 to 100AAC
0 to 200AAC
0 to 400AAC
0 to 600AAC
) is set as the default value, change the setting depending on the connected
H
CHAPTER 6 BUFFER MEMORY
Setting value
0000
0001
0002
0003
0004
0005
0010
0011
0012
0013
0014
0015
).
H
H
H
H
H
H
H
H
H
6
H
H
H
H