Mitsubishi Electric MELSEC-Q series User Manual page 200

Programmable controller current transformer input module
Hide thumbs Also See for MELSEC-Q series:
Table of Contents

Advertisement

(3) Mounting a new module
(4) Checking operation
(To the next page)
198
1.
Mount the removed module and new module to the
other system.
2.
Using the G(P).OGLOAD instruction, save the
offset/gain setting values in the user range from the
removed module to the CPU device. Refer to
Page 236, Appendix 1.2 for the G(P).OGLOAD
instruction.
3.
Using the G(P).OGSTOR instruction, restore the
offset/gain setting values in the user range to a new
module. Refer to
the G(P).OGSTOR instruction.
4.
Remove the new module from the other system,
mount it to the slot from where the old module was
removed in the original system, and install the
terminal block.
5.
After mounting the module, click the
button and make sure that the RUN LED is lit.
Module READY (X0) remains off.
1.
To check the operation, click the
button to cancel the control start.
Page 240, Appendix 1.3 for