(38)CH Logging points after trigger (Un\G1048 to Un\G1055)
Set the data points recorded from hold trigger occurs until logging holds (stops) for each channel.
For details on the logging function, refer to the following.
• Logging Function (
(a) Setting range
• Setting range: 1 to 5000
• In the channel where a setting value out of the above setting range is set, an error occurs. Then the error
code (204) is stored in Latest error code (Un\G19) and Error flag (XF) turns on. Also, logging cannot be
performed.
• When Disable (1) is set to CH Logging enable/disable setting (Un\G1000 to Un\G1007), the setting for
CH Logging points after trigger (Un\G1048 to Un\G1055) is ignored.
(b) Enabling the setting
Turn on then off Operating condition setting request (Y9) to enable the setting.
(c) Default value
All channels are set to 2500.
(39)CH Level trigger condition setting (Un\G1056 to Un\G1063)
When the level trigger is used with the logging function, set the occurrence condition of the hold trigger for each
channel.
For details on the logging function, refer to the following.
• Logging Function (
• In the channel where a setting value other than the above is set, an error occurs. The error code (205) is
stored in Latest error code (Un\G19) and Error flag (XF) turns on. Also, logging cannot be performed.
• When Disable (1) is set to CH Logging enable/disable setting (Un\G1000 to Un\G1007), the setting for
CH Level trigger condition setting (Un\G1056 to Un\G1063) is ignored.
(a) Enabling the setting
Turn on then off Operating condition setting request (Y9) to enable the setting.
(b) Default value
All channels are set to Disable (0).
128
Page 58, Section 4.12)
Page 58, Section 4.12)
Setting
Disable
Above
Below
Pass through
Setting value
0
1
2
3