8.4
Auto Refresh
This function transfers data in the buffer memory to specified devices.
Programming of reading/writing data is unnecessary.
(1) Setting procedure
Open the "Auto_Refresh" window.
1.
Start "Auto_Refresh".
Project window
2.
Click the item to set, and input the destination device for auto refresh.
Available devices are X, Y, M, L, B, T, C, ST, D, W, R, and ZR.
When a bit device X, Y, M, L, or B is used, set a number that is divisible by 16 points (example: X10, Y120, M16).
Data in the buffer memory are stored in 16 points of devices starting from the set device No. (Example: When X10 is set, the
data are stored in X10 to X1F).
[Intelligent Function Module]
CHAPTER 8 VARIOUS SETTINGS
Module Name
[Auto_Refresh]
8