When A User Range Is Used And Parameters Are Set Using A Sequence Program; (With Another System) - Mitsubishi Electric MELSEC-Q series User Manual

Programmable controller current transformer input module
Hide thumbs Also See for MELSEC-Q series:
Table of Contents

Advertisement

10.8
When a User Range Is Used and Parameters Are Set
Using a Sequence Program (with Another System)
(1) Stopping operation
CHAPTER 10 ONLINE MODULE CHANGE
1.
Open the "Device/Buffer Memory Batch Monitor"
window.
[Online]
[Monitor]
Batch]
When using GX Developer, open the "Device test"
window.
[Online]
[Debug]
2.
Enter and display the buffer memory address of
Conversion enable/disable setting (Un\G0).
3.
Set Conversion enable/disable setting (Un\G0) to
Disable (1) for all channels.
4.
Turn on Operating condition setting request (Y9).
5.
Confirm that the digital conversion has stopped
with Conversion completed flag (Un\G10).
6.
After checking Conversion completed flag (Un\G10),
check that Operating condition setting completed
flag (X9) turns off, then turn off Operating condition
setting request (Y9).
[Device/Buffer Memory
[Device test...]
201
10

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents