Mitsubishi Electric MELSEC-Q series User Manual page 66

Programmable controller current transformer input module
Hide thumbs Also See for MELSEC-Q series:
Table of Contents

Advertisement

When CH Level trigger condition setting (Un\G1056 to Un\G1063) is set to a value other than Disable
Ex.
(0) and CH1 Digital output value (Un\G11) is logged
CH1 Logging hold request
(Un\G1008)
Trigger condition
CH1 Logging data
(Un\G5000 to Un\G9999)
(6) Checking the stop of the logging
Check that CH Logging hold flag (Un\G1016 to Un\G1023) turns ON (1).
(7) Checking trigger detection time
The time at that the hold trigger was detected can be checked in the buffer memory.
Even when the logging cycle is set as less than 1s, the minimum time unit recorded in CH Trigger detection time
(Un\G1154 to Un\G1185) is second. Use trigger detection time as an indication to refer to the logging data.
*1
When the hold trigger is detected as soon as turning on the programmable controller, the CT input module may not
obtain the time in the CPU module. If the module could not obtain the time, the trigger detection time is recorded "0:0:0
on January 1st, 2000".
Trigger detection time is stored in the following buffer memory areas.
For CH1 Trigger detection time (Un\G1154 to Un\G1157)
Ex.
Un\G1154
Un\G1155
Un\G1156
Un\G1157
64
Not satisfied
The data stored before the last
5000 data are discarded.
Controlled by the CT input module
Channel
CH1
CH1 Trigger detection time (Un\G1154 to Un\G1157)
CH2
CH2 Trigger detection time (Un\G1158 to Un\G1161)
CH3
CH3 Trigger detection time (Un\G1162 to Un\G1165)
CH4
CH4 Trigger detection time (Un\G1166 to Un\G1169)
CH5
CH5 Trigger detection time (Un\G1170 to Un\G1173)
CH6
CH6 Trigger detection time (Un\G1174 to Un\G1177)
CH7
CH7 Trigger detection time (Un\G1178 to Un\G1181)
CH8
CH8 Trigger detection time (Un\G1182 to Un\G1185)
to
b15
First two digits of the year
Month
Hour
Second
OFF (0)
CH1 Number of logging data
(Un\G1106)
Address for trigger detection time
b8 b7
Last two digits of the year
Day of the week
ON (1)
Satisfied
A Hold trigger is
The logging is held.
executed.
CH1 Logging points after
trigger (Un\G1048)
5000 points
*1
b0
to
Day
Minute