8.5.2

Setting from a program

(1) Setting procedure
The following is the procedure to configure the offset/gain setting using a sequence program.
2)
Switch to the offset/gain setting mode.
Check that the module is in the
offset/gain setting mode and the RUN
LED is flashing.
Change the input range.
1)
Apply the current whose value is the
same as the offset value.
Set the target channels in Offset/gain
setting mode Offset specification
(Un\G22).
More than one channel can be set
simultaneously on the condition that "0"
is set in Offset/gain setting mode Gain
specification (Un\G23).
Turn on Channel change request (YB).
Check that Channel change completed
flag (XB) is on.
Turn off Channel change request (YB).
Apply the current whose value is the
same as the gain value.
*1
The following are the methods to switch modes (normal mode
• Dedicated Instruction (G(P).OFFGAN (
• Setting Mode switching setting (Un\G158, Un\G159) and turning on then off Operating condition setting request (Y9)
(
Page 118, Section 6.2 (21))
• Intelligent Function Module Switch Setting (
Start
Set the target channels in Offset/gain
setting mode Gain specification
(Un\G23).
*1
More than one channel can be set
simultaneously on the condition that "0"
is set in Offset/gain setting mode Offset
specification (Un\G22).
Turn on Channel change request (YB).
Check that Channel change completed
flag (XB) is on.
Turn off Channel change request (YB).
Register the offset/gain setting to the
CT input module by turning on User
range write request (YA).
Check that Offset/gain setting mode
flag (XA) is off. Then, turn off User
range write request (YA).
Check that Offset/gain setting mode
flag (XA) is on.
Switch to the normal mode.
Page 234, Appendix 1.1))
Page 143, Section 8.2)
CHAPTER 8 VARIOUS SETTINGS
YES
Adjust other channels.
NO
YES
Is the ERR. LED on?
NO
*1
End
offset/gain setting mode
1)
2)
normal mode).