6.4.10 Air handling unit

6.4.10.1 Settings
Set the type of air handling unit here. The type of air
handling unit is normally preset for the unit supplied;
except the GOLD SD extract air unit which must be set
here.
N.B.! Do not change the air handling unit setting to a
type that differs from the one supplied. If you do so, the
air handling unit will not operate satisfactorily.
The air handling unit can be given a specifi c name (e.g. the
unit's serial number). Naming in the hand-held terminal can
only be done with digits, however on the web page the naming
can also be done with alphabetical characters. The given name
is then shown in all the images in the hand-held terminal and
web page.
The type of AHU, size of the supply air and extract air fan re-
spectively can be viewed.
GOLD RX/PX/CX
The AHU's fan position 1 (left-hand fan seen from the inspection
side, see illustrations) can be read and preset.
N.B.! This changes the function of the fans from supply
air to extract air and vice versa. GOLD RX size 04-120/
GOLD RX Top can be changed at the site. The other vari-
ants must not be changed from the factory setting.
The fan position in the fl ow chart can be read and should be set
according to the AHU's actual confi guration.
GOLD SD
The fan position, upper or lower level, can be read and should be
set according to the AHU's actual confi guration.
Settings:
Value
Type of air handling unit
GOLD RX/PX/CX
Name
Fan position 1
Flow chart, supply air fan
position
GOLD SD
Name
Flowchart fan position
58
www.swegon.com
Setting
Factory
range
setting
GOLD RX/GOLD
Type of air
PX/GOLD CX/
handling
GOLD SD Sup-
unit sup-
ply air/GOLD
plied, except
SD Extract air/
the GOLD
GOLD SD Sup-
SD extract
ply air+CX/
air handling
GOLD SD Supply
unit
air+Extract air/
GOLD SD Sup-
ply air+Extract
air+CX
Optional
Extract air/
Extract air
Supply air
Upper level/
Lower level
Lower level
Optional
Upper level/
Lower level
Lower level
Air handling
unit
Settings
GOLD RX 04-40
Fan arrangement 1
Fan pos. 1 set as extract air
(right-hand inspection side)
Fan arrangement 2
Fan pos. 1 set as extract air
(right-hand inspection side)
GOLD RX Top
Fan pos. 1 set as supply air
(left-hand inspection side)
Outdoor air
Supply air
We reserve the right to alter specifi cations without notice.
GB.GOLDSKE.160901
Fan pos. 1 set as supply air
(left-hand inspection side)
Fan pos. 1 set as supply air
(left-hand inspection side)
Fan pos. 1 set as extract air
(right-hand inspection side)
Extract air
Exhaust air