Alarm text
Function
31:1 PRESSURE REGULATION, SUPPLY AIR PRESSURE SENSOR NO.
5 COMMUNICATION ERROR
The air handling unit's control unit cannot establish correct
communication with the duct pressure sensor in the supply
air. Applies only to pressure regulation of the supply air.
31:2 PRESSURE REGULATION, SUPPLY AIR PRESSURE BELOW SET
POINT ALARM LIMIT
The duct pressure has gone below its set point by more that
10%, during a longer period than 20 minutes ( if pressure
sensors are connected).
31:3 PRESSURE REGULATION, SUPPLY AIR PRESSURE ABOVE SET
POINT ALARM LIMIT
The supply air duct pressure has exceeded its set point by
more that 10%, during a longer period than 20 minutes (if
pressure sensors are connected).
31:6 PRESSURE REGULATION, EXTRACT AIR PRESSURE SENSOR
NO. 6 COMMUNICATION ERROR
The air handling unit's control unit cannot establish correct
communication with the duct pressure sensor in the extract
air. Applies only to pressure regulation of the extract air.
31:7 PRESSURE REGULATION, EXTRACT AIR PRESSURE BELOW
SET POINT ALARM LIMIT
The extract air duct pressure has gone below its set point by
more that 10%, during a longer period than 20 minutes (if
pressure sensors are connected).
31:8 PRESSURE REGULATION, EXTRACT AIR PRESSURE ABOVE
SET POINT ALARM LIMIT
The extract air duct pressure has exceeded its set point by
more that 10%, during a longer period than 20 minutes (if
pressure sensors are connected).
Alarm group 32: ReCO
/Intermittent night heating
2
32:1 ReCO
, I/O MODULE NO. 0 COMMUNICATION ERROR
2
The air handling unit's control unit cannot establish correct
communication with I/O module no. 0.
32:2 ReCO
, PRESSURE SENSOR NO. 0 COMMUNICATION ERROR
2
The air handling unit's control unit cannot establish correct
communication with the pressure sensor.
32:3 ReCO
/INTERMITTENT NIGHT HEATING, RECIRCULATED AIR
2
DAMPER MONITORING TRIPPED
The damper actuator does not move to the right position.
The position-confirming output signal from the damper is
not the same as the input control signal.
32:4 ReCO
, OUTDOOR AIR DAMPER MONITORING TRIPPED
2
The damper actuator does not move to the right position.
The position-confirming output signal from the damper is
not the same as the input control signal.
Alarm group 33: Service
33:1 PERIOD BETWEEN SERVICING PAST ALARM LIMIT
The preset service period has expired.
If the alarm is RESET via the hand-held terminal, the alarm
will be initiated again after 7 days.
A new service period can be set and reset under ALARM
SETTINGS.

We reserve the right to alter specifications without notice.

Priority
Stop
0 = Blocked 0 = In operat.
A = A alarm
1 = Stop
B = B alarm
A
1
3)
B
0
3)
B
0
3)
A
1
3)
B
0
3)
B
0
3)
A
0
3)
A
0
3)
B
0
3)
B
0
3)
B
0
3)
GB.GOLDSKE.160901
Delay
Resetting
s = second
0 = manual
m = minute
1 = automatic
h=hour
10 s
1
20 m
0
20 m
0
10 s
1
20 m
0
20 m
0
10 s
1
10 s
1
10 m
0
10 m
0
5 s
0
2)
www.swegon.com
99