Alarm text
Function
15:12 PLATE HEAT EXCHANGER, BYPASS DAMPER MONITORING
TRIPPED
The bypass damper monitoring function of the plate heat
exchanger has tripped.
15:14 PLATE HEAT EXCHANGER, DEFROSTING SENSOR NO. C
COMMUNICATION ERROR
The air handling unit's control unit cannot establish cor-
rect communication with defrosting sensor C for the heat
exchanger.
15:15 PLATE HEAT EXCHANGER, DEFROSTING PRESSURE OVER
ALARM LIMIT
The need for defrosting has been over 95% continuously for
144 minutes.
Alarm group 16: Coil heat exchangers
16:1 COIL HEAT EXCHANGER, I/O-MODULE NO. 1 COMMUNI-
CATION ERROR
The air handling unit's control unit cannot establish cor-
rect communication with I/O module No. 1 for coil heat
exchanger.
16:2 COIL HEAT EXCHANGER, TEMPERATURE SENSOR DEFECTIVE
The temperature sensor on the coil heat exchanger's
pipework package for the frost guard is defective or is not
connected.
16:3 COIL HEAT EXCHANGER, VALVE MONITORING TRIPPED
Valve actuator of the coil heat exchanger is defective.
16:4 COIL HEAT EXCHANGER, PUMP MONITORING TRIPPED
Pump of the coil heat exchanger does not go to correct posi-
tion. The position-confirming output signal from the pump is
not the same as the input control signal.
16:5 COIL HEAT EXCHANGER, I/O-MODULE NO. C COMMUNI-
CATION ERROR
The air handling unit's control unit cannot establish cor-
rect communication with I/O module No. C for coil heat
exchanger.
16:6 COIL HEAT EXCHANGER, PRESSURE SENSOR DEFECTIVE
Pressure sensor for the coil heat exchanger is defective or is
not connected.
16:7 COIL HEAT EXCHANGER, LOW PRESSURE IN FLUID CIRCUIT
Excessively low pressure in coil heat exchanger's fluid circuit.
Alarm group 17: Rotary heat exchanger
17:1 ROTARY HEAT EXCHANGER, MOTOR CONTROLLER COM-
MUNICATION ERROR
The air handling unit's control unit cannot establish correct
communication with the heat exchanger motor controller.
17:2 ROTARY HEAT EXCHANGER, DEFROSTING PRESSURE SEN-
SOR NO. 7 COMMUNICATION ERROR
The air handling unit's control unit cannot establish correct
communication with the heat exchanger pressure sensor no.
7. Applicable to the defrosting function only.
17:3 ROTARY HEAT EXCHANGER, DEFROSTING PRESSURE OVER
ALARM LIMIT
The need for defrosting has been over 95% continuously for
144 minutes.
94
www.swegon.com
Priority
Stop
0 = Blocked 0 = In operat.
A = A alarm
1 = Stop
B = B alarm
A
0
3)4)
B
0
B
1
A
1
3)4)
A
1
3)4)
A
0
3)4)
A
1
3)4)
A
0
A
0
A
0
A
1
3)4)
B
0
3)
B
1
3)4)

We reserve the right to alter specifications without notice.

GB.GOLDSKE.160901
Delay
Resetting
s = second
0 = manual
m = minute
1 = automatic
h=hour
10 m
0
10 m
1
2.4 h
0
10 s
1
3 s
1
10 m
0
20 s
0
10 s
1
10 m
1
5 m
0
10 s
1
10 s
1
2,4 h
0