Alarm Settings - Swegon GOLD RX Operation And Maintenance Instructions

Generation e rotary heat exchanger
Hide thumbs Also See for GOLD RX:
Table of Contents

Advertisement

6.4.8 Alarm settings

6.4.8.1 Fire alarms
Internal fi re alarm
The air handling unit's internal temperature sensors serve as
fi re protection thermostats. An alarm is initiated if the supply
air temperature sensor registers more than 70 °C or when the
extract air temperature sensor registers more than 50 °C.
If an external Extract air/Room temperature sensor is connected
and activated, this works parallel with the extract air temperature
sensor of the AHU.
External fi ree alarm 1 and 2
External fi re alarm 1 (Terminals 6-7) and external fi re alarm 2
(Terminals 8-9) are used for external fi re-control equipment.
Alarm reset
The resetting of internal fi re alarms as well as the external fi re
alarms 1 and 2 can be individually selected to manual or auto-
matic.
After cool
The After cool function for electric air heaters can be individually
activated, for internal fi re alarms as well as external fi re alarms 1
and 2.
Fan operation at fi re alarm
The fans of the air handling unit can be used for evacuating
smoke, etc. It is possible to individually select the type of fan
operation for each separate fi re alarm.
If the AHU is idle, the fans selected start up (10-100%), irrespec-
tive of whether stop (all types) is activated.
The AHU's damper relay is energized and the AHU's operation
relay is de-energized. The damper that should be open in event
of fi re, shall be connected to the damper relay (control unit ter-
minals 28-30). The damper that should be closed in event of fi re,
shall be connected to the operation relay (terminals 26-27 of the
control unit, potential-free contact).
Priority
The mutual priority of the internal and the external fi re alarms
can be set. If automatic is selected, this means that the fi rst input
to be activated is given priority.
54
www.swegon.com
Alarm settings
Fire alarms
Settings:
Value
Internal fi re alarm
Internal fi re alarm reset
Internal fi re alarm after
cool
External fi re alarm 1/2,
resetting
External fi re alarm 1/2,
after cool
Fan operation on an
internal fi re alarm
Supply air fan on an
internal fi re alarm
Extract air fan on an inter-
nal fi re alarm
Fan operation on external
fi re alarm 1/2
Supply air fan on external
fi re alarm 1/2
Extract air fan on external
fi re alarm 1/2
Order of priority
We reserve the right to alter specifi cations without notice.
GB.GOLDSKE.160901
Setting
Factory
range
settings
On/Off
Off
Manual/Auto
Manual
Active/Inactive
Inactive
Manual/Auto
Manual
Active/Inactive
Inactive
Inactive/Supply air/
Inactive
Extract air/Supply
air and extract air
10-100%
100%
10-100%
100%
Inactive/Supply air/
Inactive
Extract air/Supply
air and extract air
10-100%
100%
10-100%
100%
External fi re
External fi re
alarm 1/External
alarm 1
fi re alarm 2/
Internal fi re alarm/
Automatic