Page 1
GB.GOLDSKE.160901 OPERATION AND MAINTENANCE INSTRUCTIONS FOR THE GOLD RX/PX/CX/SD, GENERATION E Applicable to program version 1.20 and newer versions GOLD PX GOLD RX GOLD CX GOLD SD The document was originally written in Swedish. www.swegon.com We reserve the right to alter specifi cations without notice.
Only a qualified electrician or service personnel trained Keep the key at a safe spot separate from the air han- by Swegon shall be permitted to modify the air handling dling unit. unit in conjunction with electrical installations or the wiring of external functions.
GB.GOLDSKE.160901 2. General the GOLD RX Top are equipped with pleated, class F7 filters. The units in other variants/sizes have class F7 supply air and extract air filters made of glass fibre. 2.1 Handling of air handling The type RECOnomic rotary heat exchanger is variable speed controlled and has a temperature efficiency of up to 85%.
GB.GOLDSKE.160901 2.7 The Components of the Air Handling Units 2.7.1 GOLD RX one-piece air handling unit with rotary heat exchanger The individual components are each specified below in a simplified and diagrammatical description. Right-hand version Fig. 1a 19 20 21...
(applies to RECOfrost only) exchanger. 10 Extract air filter* 22 Temperature/air density sensor, supply air. 11 Temperature sensor, supply air (to be mounted in supply air 23 Temperature/air density sensor, extract air. duct) www.swegon.com We reserve the right to alter specifications without notice.
10 Temperature sensor, supply air (to be mounted in supply air 25 Temperature/air density sensor, extract air. duct) GOLD CX, sizes 100/120: Pipework package including control box are supplied in unmounted condition for floor or wall mounting (accessories). www.swegon.com We reserve the right to alter specifications without notice.
Pressure sensor, supply air fan* (Position on function selector 10 Supply air filter, if applicable* switch = 2) (In extract air handling units: Extract air filter) (In extract air handling units: Pressure sensor, extract air fan) www.swegon.com We reserve the right to alter specifications without notice.
(Not used in extract air handling units) 12 Supply air filter*, if applicable SUPPLY AIR* (In extract air handling units: Extract air filter) (In extract air handling units: Exhaust air) www.swegon.com We reserve the right to alter specifications without notice.
(Not used in extract air handling units) 12 Supply air filter*, if applicable SUPPLY AIR* (In extract air handling units: Extract air filter) (In extract air handling units: Exhaust air) www.swegon.com We reserve the right to alter specifications without notice.
However, in many cases, these settings need to be adjusted to suit the current installation. 3. Check that rotary heat exchanger rotor (only GOLD RX) rotates easily. On sizes 50-120, the rotary heat exchanger If necessary, enter the fan position setting (inspection side), must be angled slightly towards the filter, see drawing below.
= flow reading (l/s) When commissioning has been completed, 3 air devices and one branch damper should stand fully open to obtain the lowest possible pressure in the system. K (Quotient) = www.swegon.com We reserve the right to alter specifications without notice.
Two commissioning plates are supplied together with the GOLD RX Top. Which commissioning plate is to be mounted is determined by whether the air handling unit is a left-hand or right-hand version unit.
11-120 units they are inside in the centre section of the unit. When you combine the GOLD RX Top 04-12 with the COOL DX Top, note that the pressure measurement tappings are located inside the centre section of the air handling unit.
(accessory) RJ45 connection for power and com- munication cable for IQnavigator (PoE) or connection to the network (requires a TBLZ-1-70 net adapter accessory) www.swegon.com We reserve the right to alter specifi cations without notice.
Status FORCING Operation level Supply air Regulation mode Extract air Boost UNIT Unit Unit Air adjustments AIRFLOW ADJUSTMENTS Outdoor air compensation Required time Booster diffusers Remaining time min. www.swegon.com We reserve the right to alter specifications without notice.
The current time/date, type of air handling unit and the name of the plant are displayed along the upper edge of the touch screen. See also Section 6.4.10.1. www.swegon.com We reserve the right to alter specifi cations without notice.
Decimal point Cancel Done Deletes previous character Decreases the highlighted value Increases the highlighted value Minus sign. Used for writing negative values. Unspecified value. Used for the time and schedule function. www.swegon.com We reserve the right to alter specifications without notice.
Dashboard N.B.! The appearance of the image Timer, low speed varies depending on the type of air han- dling unit and functions selected. Stop Alarm log Log graph Flow chart www.swegon.com We reserve the right to alter specifications without notice.
4.2.2.3 Alarm log Active alarms, pending alarms and alarm history (50 latest) can be viewed under Alarm log. See also Section 8. www.swegon.com We reserve the right to alter specifications without notice.
The circulation pump of the air heater can be hidden by clicking on the air heater symbol. The grey-marked components with green frame are inactive. These can be activated by tapping the desired component. Edit button Component with green frame www.swegon.com We reserve the right to alter specifications without notice.
Energy Stop Airflow Temperature Filters Software schedule monitoring Filter Language Alarm log calibration Log graph Flow chart Filter calibration. Dashboard. Functions. Se avsnitt 5.2 Se avsnitt 4.2.2 See Section 5.3 www.swegon.com We reserve the right to alter specifications without notice.
2) If pressure regulation is used, the airfl ow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa). 3) Cap. variant 1/cap.variant 2 www.swegon.com We reserve the right to alter specifi cations without notice.
Extract related supply air-2 Y2 10-40 °C 18 °C Extract related supply air-2 Y3 10-40 °C 14 °C Extract related supply air-2 Y4 10-40 °C 12 °C X = Extract air temperature °C www.swegon.com We reserve the right to alter specifi cations without notice.
Page 26
Outdoor related extract air Y2 10 – 40 °C 21.5 °C Outdoor related extract air Y3 10 – 40 °C 21,5 °C Outdoor related extract air Y4 10 – 40 °C 21,5 °C www.swegon.com We reserve the right to alter specifications without notice.
Preselected operating Total stop/Low Low speed mode speed/High speed/ Normal Stop/ Extended Normal Stop Start date Active/Inactive Inactive Start date Year/Month/Day Stop date Active/Inactive Inactive Stop date Year/Month/Day www.swegon.com We reserve the right to alter specifi cations without notice.
See next chapter Start weekday Each day/ Each day Calender 2 See next chapter Monday/Tuesday/ Wednesday/ Thursday/Friday/ Saturday/Sunday Stop date Year/Month/Day Stop weekday Each day/ Each day Monday/Tuesday/ Wednesday/ Thursday/Friday/ Saturday/Sunday www.swegon.com We reserve the right to alter specifications without notice.
The required time in hours and minutes can be set as follows. Settings: Value Setting Factory range setting Ext. low speedt 0:00 - 23:59 0:00 Ext. high speed 0:00 - 23:59 0:00 (hrs.:min.) (hrs.:min.) www.swegon.com We reserve the right to alter specifications without notice.
AHU is started up. How- ever, the language setting can be changed at any time. Language Settings: Value Setting Factory range setting Language Available English languages are displayed www.swegon.com We reserve the right to alter specifi cations without notice.
SMART Link Air humidity ReCO MIRU Control Log graph Flow chart Comfort recovery Dashboard. Functions. Main setup. Filter calibration. Se avsnitt 4.2.2. See Section 6.4 See Section 6.2. See Section 6.3. www.swegon.com We reserve the right to alter specifications without notice.
2) If pressure regulation is used, the airfl ow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa). 3) Cap. variant 1/cap.variant 2 www.swegon.com We reserve the right to alter specifi cations without notice.
Settings: Value Settings Supply air Airflow Duct pressure Demand Slave Extract air Airflow Duct pressure Demand Slave www.swegon.com We reserve the right to alter specifications without notice.
This is practical when making airflow adjustments in the duct system and air terminals. The desired period is preset, but can be interrupted earlier by selecting Stop or by changing the time setting to 0. www.swegon.com We reserve the right to alter specifications without notice.
Y2, breakpoint, extract air 20-750 Pa 100 Pa Y3, breakpoint, extract air 20-750 Pa 100 Pa Y4, breakpoint, extract air 20-750 Pa 100 Pa See table for min./max. flows in Section 6.4.1.2 www.swegon.com We reserve the right to alter specifications without notice.
The extract airflow is corrected by continuously measuring the pressure balance across the rotary heat exchanger. The extract airflow is guaranteed with consideration given to the air purging and leakage air flow. www.swegon.com We reserve the right to alter specifications without notice.
19 °C (step 2). breakpoint (refers to extract air temperature) The setting range for breakpoint and deviation are limited by the min. and max. settings. www.swegon.com We reserve the right to alter specifi cations without notice.
Page 39
COM1-3). Settings: Value Setting Factory range setting Extract air (temp. set point) 0-40 °C 21 °C Supply air, min. 0-20 °C 16 °C Supply air, max. 8-50 °C 28 °C www.swegon.com We reserve the right to alter specifications without notice.
Page 40
20 °C (Y3) down to 18 °C (Y4) as shown in the curve. If the outdoor air temperature is over 30 °C (X4), the extract air temperature set point will constantly be 18 °C (Y4). www.swegon.com We reserve the right to alter specifications without notice.
Control signal 5 V DC: No change in set point. Control signal 10 V DC: The set point increases by 5 °C. Value Setting Factory range setting Set point displacement On/Off www.swegon.com We reserve the right to alter specifications without notice.
Outdoor air sensor 1 On/Off Outdoor air sensor 2 On/Off Outdoor air sensor 3 On/Off Outdoor air sensor 4 On/Off Outdoor air sensor function Medium/min./Max. Medium Outdoor temperature from On/Off communication www.swegon.com We reserve the right to alter specifications without notice.
Assumes inclusion of the TCBR air recirculation section accessory. Reheating: Air heater for reheating provides heating capacity. Down regulation of fan: Down regulation can be selected for supply air only or supply air and extract air. www.swegon.com We reserve the right to alter specifications without notice.
See separate installation instructions for the TBLZ-1-58-aa Inter- nal temperature sensor. Settings: Value Setting Factory range setting Min. exhaust air On/Off Min. exhaust air temperature -40 – + 20,0 °C 5.0 °C www.swegon.com We reserve the right to alter specifications without notice.
3 K (preset at factory) lower than the preset max. supply air temperature. Settings: Value Setting Factory range setting Heating Boost On/Off Start limit 2-10 K www.swegon.com We reserve the right to alter specifications without notice.
The comfort variant, economy variant and the squence vari- comfort/ ant can be combined. The function that has the highest signal Comfort, economy (highest setpoint) applies. and sequence Start limit (Comfort) 2-10 K www.swegon.com We reserve the right to alter specifications without notice.
50% of max. supply air for AHU alt. 100 Pa The setting range is the same as the AHU's min./max. setting for flow regulation and 10-750 Pa for pressure regulation www.swegon.com We reserve the right to alter specifications without notice.
10 °C Extract air, start 17 - 27 °C 22 °C Extract air, stop 12 - 22 °C 16 °C Supply air, set point 0 - 20 °C 10 °C www.swegon.com We reserve the right to alter specifications without notice.
Down regulation can take place to max. of 50% of the preset value, however not lower than the min. flow or 20 Pa. Settings: Value Setting Factory range setting Down regulation Inactive/Supply Supply air air/Supply air and extract air www.swegon.com We reserve the right to alter specifications without notice.
Preselected operating Total stop/Low Low speed mode speed/High speed/ Normal Stop/ Extended Normal Stop Start date Active/Inactive Inactive Start date Year/Month/Day Stop date Active/Inactive Inactive Stop date Year/Month/Day www.swegon.com We reserve the right to alter specifi cations without notice.
See next chapter Start weekday Each day/ Each day Calender 2 See next chapter Monday/Tuesday/ Wednesday/ Thursday/Friday/ Saturday/Sunday Stop date Year/Month/Day Stop weekday Each day/ Each day Monday/Tuesday/ Wednesday/ Thursday/Friday/ Saturday/Sunday www.swegon.com We reserve the right to alter specifications without notice.
The required time in hours and minutes can be set as follows. Settings: Value Setting Factory range setting Ext. low speedt 0:00 - 23:59 00:00 Ext. high speed 0:00 - 23:59 00:00 (hrs.:min.) (hrs.:min.) www.swegon.com We reserve the right to alter specifications without notice.
After that every time fi lters are replaced. See also Section 6.3. Pre-fi lter/AHU fi lter (GOLD SD)/End fi lter Filter monitoring must be activated for the fi lter (in addition to the internal fi lter in the GOLD RX/PX/CX) to be monitored. Settings: Value Setting...
Extract air fan on external 10-100% 100% fi re alarm 1/2 Order of priority External fi re External fi re alarm 1/External alarm 1 fi re alarm 2/ Internal fi re alarm/ Automatic www.swegon.com We reserve the right to alter specifi cations without notice.
AHU shall stop or not in event of an alarm can be set under Alarm priority, se Section 6.4.8.6. For the GOLD RX unit, it is possible to use a separate sensor and its wiring is routed to the control unit. Select sensor input 4 for supply air = right and select sensor input 3 for supply air = left.
1:1 - 60:10 Active On/Off Priority Info*/A/B Air handling unit stop On/Off * Alarms are indicated as a flashing red LED on the hand-held terminal, no group alarm is forwarded. www.swegon.com We reserve the right to alter specifications without notice.
FTP address. Settings: Value Setting Factory range setting Log sender active On/Off Live mode E-mail/FTP/E-mail E-mail and FTP Other settings can be entered in the AHU's web page. www.swegon.com We reserve the right to alter specifi cations without notice.
N.B.! This changes the function of the fans from supply air to extract air and vice versa. GOLD RX size 04-120/ GOLD RX Top can be changed at the site. The other vari- ants must not be changed from the factory setting.
By first starting up the extract air fan and the heat exchanger, you can avoid chilling the prem- ises with supply air on a start up under cold weather conditions. www.swegon.com We reserve the right to alter specifications without notice.
Periodic operation of valve On/Off Periodic operation interval 0-168 hrs. 24 hrs. Periodic operation period 0-60 min. 3 min. Alarm input, function Inactive/Alarm Inactive on open contact/ Alarm on closed contact/Contactor function www.swegon.com We reserve the right to alter specifi cations without notice.
Periodic operation of valve On/Off Periodic operation interval 0-168 hrs. 24 hrs. Periodic operation period 0-60 min. 3 min. Pump alarm Inactive/Alarm Inactive on open contact/ Alarm on closed contact/Contactor function www.swegon.com We reserve the right to alter specifications without notice.
Periodic operation of valve On/Off Periodic operation interval 0-168 hrs. 24 hrs. Periodic operation period 0-60 min. 3 min. Alarm input, function Inactive/Alarm Inactive on open contact/ Alarm on closed contact/Contactor function www.swegon.com We reserve the right to alter specifications without notice.
Frost guard function, air heater for water The frost guard function is always active if the connected air heater for hot water has been supplied by Swegon. The function activates a heating device that keeps the tempera- ture in the coil at 13 °C while the air handling unit is operat- ing and 25 °C in the coil when the unit is stopped.
Periodic operation of valve On/Off Periodic operation interval 0-168 hrs. 24 hrs. Periodic operation period 0-60 min. 3 min. Pump alarm Inactive/Alarm Inactive on open contact/ Alarm on closed contact/Contactor function www.swegon.com We reserve the right to alter specifi cations without notice.
Periodic operation of pump 1 On/Off Periodic operation of pump 2 On/Off Periodic operation of valve On/Off Periodic operation interval 0-168 hrs. 24 hrs. Periodic operation period 0-60 min. 3 min. www.swegon.com We reserve the right to alter specifications without notice.
IQlogic module in the COOL DX chiller. Settings: Value Setting Factory range setting COOL DX Inactive/Economy/ Inactive Comfort/COOL DX Top www.swegon.com We reserve the right to alter specifications without notice.
0 - Max. flow 75% of max. airflow step 3 for air handling unit Extract air, On/Off, 0 - Max. flow 75% of max. airflow step 3 for air handling unit www.swegon.com We reserve the right to alter specifications without notice.
If the fans are generating low airfl ows, the rotary heat exchanger is decelerated to an appropriate speed to ensure a correct purging airfl ow through the heat exchanger. Settings: Value Setting Factory range setting Carry over control On/Off www.swegon.com We reserve the right to alter specifi cations without notice.
Settings: Value Setting Factory range setting Defrost On/Off Defrost limit value 30 - 100 Pa 50 Pa Calibration On/Off www.swegon.com We reserve the right to alter specifications without notice.
6.4.13.5 Glycol (CX) Glycol The type of glycol and the content of glycol can be set here. Settings: Value Setting Factory range settings Type of glycol Ethylene/Propylene Ethylene Content of glycol 20/30/40% www.swegon.com We reserve the right to alter specifications without notice.
6.4.13.7 Automatic functions Anti-frost protection In cold weather, and if the extract air is humid, there is risk of GOLD RX (rotary heat exchanger) frosting in the coil heat exchanger. The GOLD CX/SD is equipped Purging function with anti-frosting protection.
For more information concerning waterborne heat pumps/chill- ers, see the Guide to the SMART Link/AQUA Link Functions. For more information concerning DX heat pumps/chillers (Celest LE), see the Guide to the SMART Link DX (GOLD RX only) Func- tions. Settings:...
Steam humidifi cation (0 - 10V) The function is appropriate for operation together with a steam humidifi er (not supplied by Swegon) and is a variable control sys- tem via 0-10 V control signal, as well as a contact function which...
Open circuit involves opening the circuit in order to initi- ate an alarm. Contactor function involves the use of an auxiliary contact from a contactor, which controls the humidifier. The aux. contact is connected to the alarm input. www.swegon.com We reserve the right to alter specifications without notice.
Min. exhaust air 25% of max. airfl ow for air handling unit Calibration On/Off The setting range is the same as the AHU's min. - max. set- tings. www.swegon.com We reserve the right to alter specifi cations without notice.
Page 76
0-60 min. 3 min. Pump alarm Inactive/Alarm Inactive on closed con- tact/Alarm on Omitted if the outdoor temperature compensation open contact/ is selected. Contactor func- tion Valve alarm On/Off www.swegon.com We reserve the right to alter specifi cations without notice.
Tue., High speed Wed., etc. High speed, Mon. – Fri. High speed, Sat. – Sun. High speed, Mon. – Sun. Start time 00:00-00:00 00:00 Stop time 00:00-00:00 00:00 www.swegon.com We reserve the right to alter specifi cations without notice.
1 Temperature On/Off sensor no. 2 * If analogue inputs 1 and 2 are both selected for setpoint dis- placement, only analogue input 1 will be used. www.swegon.com We reserve the right to alter specifi cations without notice.
Internet Explorer. Further information about interfaces, protocols and con- fi guration is available at www.swegon.se (com). 6.4.20.1 External Port B External Port B For communication with network. Specify protocol and settings for Ethernet.
Approved client netmask 0.0.0.0 6.4.20.6 BACnet IP BACnet IP Enter the BACnet IP settings. Settings: Value Factory setting Network number Ext. B Internal network number A Device ID Port number 47808 www.swegon.com We reserve the right to alter specifications without notice.
Operation level It is possible to change the operation level communication here. ommunication Settings: Value Setting range Factory setting Operation level Inactive/Total stop/Low Inactive communication speed/High speed/Normal stop/ Extended normal stop www.swegon.com We reserve the right to alter specifications without notice.
The requirements for password can be activated here under User level (local). The password is always 0000. Settings: Users Value Setting Factory range setting Requirements for user password On/Off IQnavigator user www.swegon.com We reserve the right to alter specifi cations without notice.
On a return to the other image groups, the controller resumes normal operation and all settings for manual testing will be terminated. Each image indicates which functions can be test run. www.swegon.com We reserve the right to alter specifi cations without notice.
Button sound effects on the hand-held terminal can be activated and the volume can be set in fi ve steps. Settings: Value Setting Factory range settings Button sound effects On/Off Volume www.swegon.com We reserve the right to alter specifi cations without notice.
Order new filters from Swegon or your nearest Swegon rep- resentative. Specify the size of the GOLD unit, whether the replacement concerns one or two directions of airflow and if you are replacing standard filters and/or possibly a pre-filter.
Only service person- This cleaning agent is sold by Swegon Service. nel trained by Swegon shall be permitted to wash it in this way. While cleaning, check whether venting is necessary, check the Vinyl-coated fabric seal content of glycol in the water and the condition of the coil for Lift up the fabric seal and inspect its underside.
Alarms that reset themselves automatically will do so as soon as the fault has been remedied. Alarms can also be reset via a communication network (not applicable to frost guard alarm). 8.1.3 Changing alarm settings See Section 6.4.8.6. www.swegon.com We reserve the right to alter specifications without notice.
I/O module No. E for extra regulation sequence. EXTRA REGULATION SEQUENCE 1, OVERHEATING PROTEC- 10 s TION FOR ELECTRIC AIR HEATER TRIPPED Overheating protection, electric air heater, has tripped. www.swegon.com We reserve the right to alter specifications without notice.
REHEAT, FROST GUARD TEMPERATURE SENSOR DEFECTIVE Frost guard temperature sensor is defective or is not con- nected. REHEAT, VALVE MONITORING TRIPPED 10 m Valve actuator, air heater for water is defective. www.swegon.com We reserve the right to alter specifications without notice.
Xzone, COOL, ALARM INPUT 2 TRIPPED 20 s Alarm input 2 Xzone cool has tripped. Alarm group 8: Cooling COOLING, VALVE MONITORING TRIPPED 10 s Valve actuator, air cooler, is defective. Alarm group 9: Spare www.swegon.com We reserve the right to alter specifications without notice.
10:3 EXTRACT AIR TEMPERATURE SENSOR DEFECTIVE Extract air sensor is defective or is not connected. 10:4 EXTRACT AIR TEMPERATURE SENSOR FOR DENSITY COM- PENSATION DEFECTIVE (GOLD RX/PX/CX) Temperature sensor in extract air fan intake cannot establish correct communication or shows incorrect value.
The humidity sensor in the supply air duct is defective or is not connected. 13:3 EXTRACT AIR HUMIDITY SENSOR DEFECTIVE 10 s The humidity sensor in the extract air duct is defective or is not connected. www.swegon.com We reserve the right to alter specifications without notice.
15:11 PLATE HEAT EXCHANGER, I/O-MODULE NO. 3 COMMUNI- 10 s 3)4) CATION ERROR The air handling unit's control unit cannot establish correct communication with I/O module No. 3 for the plate heat exchanger. www.swegon.com We reserve the right to alter specifications without notice.
7. Applicable to the defrosting function only. 2,4 h 17:3 ROTARY HEAT EXCHANGER, DEFROSTING PRESSURE OVER 3)4) ALARM LIMIT The need for defrosting has been over 95% continuously for 144 minutes. www.swegon.com We reserve the right to alter specifications without notice.
Heating water temperature is below preset set point longer than 30 minutes. 18:13 AYC COOLING, TEMPERATURE ABOVE SET POINT ALARM 30 m LIMIT Cooling water temperature exceeds preset set point longer than 30 minutes. www.swegon.com We reserve the right to alter specifications without notice.
Alarm group 22: Spare Alarm group 23: SMART Link 23:1 SMART Link, COMMUNICATION ERROR 30 s The air handling unit’s control unit cannot establish correct communication with the chiller/heat pump. www.swegon.com We reserve the right to alter specifications without notice.
27:1 AHU FILTER, SUPPLY AIR PRESSURE SENSOR NO. 3/4 COM- 10 s MUNICATION ERROR The air handling unit's control unit cannot establish correct communication with the sensor of the AHU supply air filter. www.swegon.com We reserve the right to alter specifications without notice.
30:11 AIRFLOW MEASUREMENT, PURGING PRESSURE SENSOR NO. B COMMUNICATION ERROR The air handling unit's control unit cannot establish correct communication with the sensor of the rotary heat exchanger purging sector. Alarm group 31: Pressure regulation www.swegon.com We reserve the right to alter specifications without notice.
If the alarm is RESET via the hand-held terminal, the alarm will be initiated again after 7 days. A new service period can be set and reset under ALARM SETTINGS. www.swegon.com We reserve the right to alter specifications without notice.
B = B alarm h=hour 33:15 LOCK FUNCTION TRIPPED – – – Contact Swegon or their representative. Alarm group 34: External controls 10 s 34:1 EXTERNAL CONTROL, I/O MODULE NO. 3 COMMUNICA- TION ERROR The air handling unit's control unit cannot establish correct communication with I/O module No.
PHASE VOLTAGE High voltage difference between the phases (3-phase, 400 V), which causes rippling. SUPPLY AIR FAN 1-3/A-B MOTOR CONTROLLER PHASE 10 s 54:8 FAILURE Phase failure in motor controller. www.swegon.com We reserve the right to alter specifications without notice.
EXTRACT AIR FAN 1-3/A-B MOTOR CONTROLLER CURRENT 60 s 60:10 LIMITATION Current/Voltage limitation in motor controller. EXTRACT AIR FAN 1A-3A MOTOR CONTROLLER INTERNAL 57:11 COMMUNICATION ERROR Internal communication error in motor controller. www.swegon.com We reserve the right to alter specifications without notice.
Stops the AHU if the temperature is below the adjustable limit. Inactive as factory setting. Contact Swegon or their representative. Alarm group 38 = MIRU Control 1. Alarm group 39 = MIRU Control 2. Alarm group 40 = MIRU Control 3. Alarm group 41 = MIRU Control 4.
Recurrent at 30 minute intervals. Message is not received after completed ReCO calibration. 98:14 ReCO CALIBRATION FAILURE ReCO calibration failure. Recurrent at 5 second intervals. www.swegon.com We reserve the right to alter specifications without notice.
The SD card's memory is full. The oldest log data is being deleted. 99:14 INTERNAL SERIAL MEMORY ERROR CPEx1 Internal serial memory error CPEx1 99:15 CLOCK CIRCUIT DEFECTIVE Circuit for the clock is defective www.swegon.com We reserve the right to alter specifications without notice.
GB.GOLDSKE.160901 10. Technical Data 10.1 Dimensions, GOLD RX one-piece air handling unit with rotary heat exchanger GOLD 04/05, 07/08 * The air handling unit is supplied without end connection panel if a duct accessory housed in GOLD GOLD an insulated casing will be connected.
* The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected. Size Weight, kg 1126 3340 1070 1200 2400 3440 3322 2500 1720 3540-3900 1126 3340 1070 1200 2400 3440 3322 2500 1720 3746-4168 www.swegon.com We reserve the right to alter specifications without notice.
** Width of centre section's casing = B + 200 mm. Size Weight, kg 1126 3340 1144 1200 2400 3440 3396 2500 1720 4374-4734 1126 3340 1144 1200 2400 3440 3396 2500 1720 4580-5002 www.swegon.com We reserve the right to alter specifications without notice.
GOLD Size Weight, kg Weight, kg Weight, kg fan + filter fan + filter + coil 169-188 254-292 480-518 187-206 272-310 498-536 Size 14/20 1040 1875 2615 1400 1136 1000 www.swegon.com We reserve the right to alter specifications without notice.
Weight, kg Weight, kg Weight, kg fan + filter fan + filter + coil 379-410 558-620 1093-1155 419-450 589-660 1133-1195 Size 50/60 1078 1947 2687 2166 2318 1320 1050 1600 www.swegon.com We reserve the right to alter specifications without notice.
+ fan power conn. + fan 899-1079 1428-1608 2187-2367 1048 1000 1048 1002-1213 1531-1742 2290-2501 3186 Size 100/120 1682 2752 3396 3340 1620 1126 1144 1126 1200 2400 2500 www.swegon.com We reserve the right to alter specifications without notice.
(RX/PX/CX). GOLD 100/120: If more than 16 VA is required, use wiring terminals 201 (G) and 202 (G0). Terminals 201-202 can be loaded with a total of max. 48 VA. www.swegon.com We reserve the right to alter specifications without notice.
GOLD 35, capacity variant 1: 3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 20 AT GOLD 35, capacity variant 2: 3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 20 AT (RX), 25 AT (CX) www.swegon.com We reserve the right to alter specifications without notice.
GOLD 120, capacity variant 2: alt. Motor shaft power: 2 x 6.5 kW, 3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 63 AT motor controller: 3 x 400 V, 50 Hz www.swegon.com We reserve the right to alter specifications without notice.
GB.GOLDSKE.160901 11. Appendices 11.1 Declaration of Conformity 11.1.1 GOLD RX EC DECLA ARATION OF CON NFORMIT TY FOR MAC CHINERY Original Directive 200 06/42/EC, Ann nex II 1A Manufacture er (and where appropriate h his authorised representativ ve): Company: Swegon AB Address: Box 300, SE- -53523 Kvänu Hereby decla...
CHINERY Original Directive 200 06/42/EC, Ann nex II 1A Manufacture er (and where appropriate h his authorised representativ ve): Company: Swegon AB Address: Box 300, SE- -53523 Kvänu Hereby decla ares that: Type of mac chinery: Air handling g units No. of mach hinery: GOLD 04/05...
CHINERY Original Directive 200 06/42/EC, Ann nex II 1A Manufacture er (and where appropriate h his authorised representativ ve): Company: Swegon AB Address: Box 300, SE- -53523 Kvänu Hereby decla ares that: Type of mac chinery: Air handling g units No. of mach hinery: GOLD 35/40...
CHINERY Original Directive 200 06/42/EC, Ann nex II 1A Manufacture er (and where appropriate h his authorised representativ ve): Company: Swegon AB Address: Box 300, SE- -53523 Kvänu Hereby decla ares that: Type of mac chinery: Air handling g units No. of mach hinery: GOLD 04/05...
GB.GOLDSKE.160901 11.2 Commissioning Record Is also available in digital form at www.swegon.com Company Our reference Client Date SO No. Plant Project/Air handling unit Series no.: Plant address Type/size Program version: Filter calibration performed Timer, current time preset Other controls www.swegon.com...
Page 125
+10°C X4, breakp., outd. temp. °C +20°C 1) Low speed = 25%, high speed = 50% and max. speed = 75 % of max. fl ow, see Section 5.3.1.2 www.swegon.com We reserve the right to alter specifi cations without notice.
Y3, breakp., supply air Y4, breakp., supply air Extract air, pressure Y1, breakp., extract air Y2, breakp., extract air Y3, breakp., extract air Y4, breakp., extract air Booster diffusers Booster diffusers X Off www.swegon.com We reserve the right to alter specifications without notice.
Page 127
Extract air (temp. set point) °C Supply air, min. °C Supply air, max. °C Xzone, Extract air (temp. set point) °C Xzone, Supply air, min. °C Xzone, Supply air, max. °C www.swegon.com We reserve the right to alter specifi cations without notice.
External temperature sensors Extract air duct, temperature sensor X Off Room sensor 1 X Off Room sensor 2 X Off Room sensor 3 X Off Room sensor 4 X Off www.swegon.com We reserve the right to alter specifications without notice.
°C Extract air stop °C Supply air, set point °C Down regulation (airflow/pressure) Down regulation X Supply air Inactive Inactive Supply air Supply and extract air Supply and extract air www.swegon.com We reserve the right to alter specifications without notice.
Page 130
00:00 Event 6 X Inactive Total Stop Inactive Total Stop Low speed High Speed Low speed High Speed Normal Stop Extended Normal Stop Normal Stop Extended Normal Stop www.swegon.com We reserve the right to alter specifi cations without notice.
Time, Event 6 hour:min 00:00 Event 6 X Inactive Total Stop Inactive Total Stop Low speed High Speed Low speed High Speed Normal Stop Extended Normal Stop Normal Stop Extended Normal Stop www.swegon.com We reserve the right to alter specifications without notice.
Time, Event 6 hour:min 00:00 Event 6 X Inactive Total Stop Inactive Total Stop Low speed High Speed Low speed High Speed Normal Stop Extended Normal Stop Normal Stop Extended Normal Stop www.swegon.com We reserve the right to alter specifications without notice.
Time, Event 6 hour:min 00:00 Event 6 X Inactive Total Stop Inactive Total Stop Low speed High Speed Low speed High Speed Normal Stop Extended Normal Stop Normal Stop Extended Normal Stop www.swegon.com We reserve the right to alter specifications without notice.
Time, Event 6 hour:min 00:00 Event 6 X Inactive Total Stop Inactive Total Stop Low speed High Speed Low speed High Speed Normal Stop Extended Normal Stop Normal Stop Extended Normal Stop www.swegon.com We reserve the right to alter specifications without notice.
Month 1-12 Each Day 1-7 8-14 15-21 22-28 29-31 Start weekday X Each day Monday Tuesday Each day Monday Tuesday Wednesday Thursday Friday Wednesday Thursday Friday Saturday Sunday Saturday Sunday www.swegon.com We reserve the right to alter specifications without notice.
Mon 1-12 Each Day 1-7 8-14 15-21 22-28 29-31 Start weekday X Each day Monday Tuesday Each day Monday Tuesday Wednesday Thursday Friday Wednesday Thursday Friday Saturday Sunday Saturday Sunday www.swegon.com We reserve the right to alter specifications without notice.
Mon 1-12 Each Day 1-7 8-14 15-21 22-28 29-31 Start weekday X Each day Monday Tuesday Each day Monday Tuesday Wednesday Thursday Friday Wednesday Thursday Friday Saturday Sunday Saturday Sunday www.swegon.com We reserve the right to alter specifications without notice.
Mon 1-12 Each Day 1-7 8-14 15-21 22-28 29-31 Start weekday X Each day Monday Tuesday Each day Monday Tuesday Wednesday Thursday Friday Wednesday Thursday Friday Saturday Sunday Saturday Sunday www.swegon.com We reserve the right to alter specifications without notice.
Mon 1-12 Each Day 1-7 8-14 15-21 22-28 29-31 Start weekday X Each day Monday Tuesday Each day Monday Tuesday Wednesday Thursday Friday Wednesday Thursday Friday Saturday Sunday Saturday Sunday www.swegon.com We reserve the right to alter specifications without notice.
Mon 1-12 Each Day 1-7 8-14 15-21 22-28 29-31 Start weekday X Each day Monday Tuesday Each day Monday Tuesday Wednesday Thursday Friday Wednesday Thursday Friday Saturday Sunday Saturday Sunday www.swegon.com We reserve the right to alter specifications without notice.
Mon 1-12 Each Day 1-7 8-14 15-21 22-28 29-31 Start weekday X Each day Monday Tuesday Each day Monday Tuesday Wednesday Thursday Friday Wednesday Thursday Friday Saturday Sunday Saturday Sunday www.swegon.com We reserve the right to alter specifications without notice.
Mon 1-12 Each Day 1-7 8-14 15-21 22-28 29-31 Start weekday X Each day Monday Tuesday Each day Monday Tuesday Wednesday Thursday Friday Wednesday Thursday Friday Saturday Sunday Saturday Sunday www.swegon.com We reserve the right to alter specifications without notice.
Mon 1-12 Each Day 1-7 8-14 15-21 22-28 29-31 Start weekday X Each day Monday Tuesday Each day Monday Tuesday Wednesday Thursday Friday Wednesday Thursday Friday Saturday Sunday Saturday Sunday www.swegon.com We reserve the right to alter specifications without notice.
Mon 1-12 Each Day 1-7 8-14 15-21 22-28 29-31 Start weekday X Each day Monday Tuesday Each day Monday Tuesday Wednesday Thursday Friday Wednesday Thursday Friday Saturday Sunday Saturday Sunday www.swegon.com We reserve the right to alter specifications without notice.
Mon 1-12 Each Day 1-7 8-14 15-21 22-28 29-31 Start weekday X Each day Monday Tuesday Each day Monday Tuesday Wednesday Thursday Friday Wednesday Thursday Friday Saturday Sunday Saturday Sunday www.swegon.com We reserve the right to alter specifications without notice.
Page 146
Supply air pre-fi lter Extract air pre-fi lter Supply air AHU fi lter Extract air AHU fi lter Supply air end fi lter Language Function Factory-preset value Adjusted value Language Language English www.swegon.com We reserve the right to alter specifi cations without notice.
Page 147
Supply air below set point Supply air above set point Extract air below alarm limit °C 12.0 Outdoor temperature limit stop °C Service period Service period Mon. 12 Alarm priority See alarm list www.swegon.com We reserve the right to alter specifi cations without notice.
Page 148
Function Factory-preset value Adjusted value Air handling unit Type of air handling unit Type of air handling unit supplied, GOLD RX GOLD PX except the GOLD SD extract air han- GOLD CX GOLD SD Supply air dling unit GOLD SD Extract air...
Page 149
Extra regul.seq. 1 closed cont. closed cont. Extra regul.seq. 1 Extra regul.seq. 1 Extra regul.seq. 1 Extra regul.seq. 1 closed cont. manual closed cont. manual Extra reg. sequence X Off www.swegon.com We reserve the right to alter specifi cations without notice.
Page 150
COOL DX X Inactive Economy Comfort Inactive Economy Comfort COOL DX Top COOL DX Top Delay time Restart time min. 5 Step switch time min. 5 Stop/start time min. 5 www.swegon.com We reserve the right to alter specifi cations without notice.
Page 151
Glycol (CX) Type of glycol X Ethylene Propylene Ethylene Propylene Content of glycol X 30 Calibration/Optimization (PX) Calibration X Off Bypass optimization X Off www.swegon.com We reserve the right to alter specifi cations without notice.
Page 152
Alarm on open contact Contactor function DX (Celest+) Amount of units Comfort mode, durationmin Outdoor air limit °C (not applicable to the chiller) Defrost delay Dead band, supply air temp. Stabilization time www.swegon.com We reserve the right to alter specifi cations without notice.
Page 153
X Off Temperature Min. outdoor air 25% of max. airfl ow for air handling unit Min. exhaust air 25% of max. airfl ow for air handling unit Calibration X Off www.swegon.com We reserve the right to alter specifi cations without notice.
Page 154
Pump alarm X Inactive Alarm on closed cont. Inactive Alarm on closed cont. Alarm on open contact Alarm on open contact Contactor function Contactor function Valve alarm X Off www.swegon.com We reserve the right to alter specifi cations without notice.
Page 155
Alarm on open contact Alarm on open contact Contactor function Contactor function Valve alarm X Off MIRU Control Function Factory-preset value Adjusted value MIRU Control See the commissioning report for MIRU Control www.swegon.com We reserve the right to alter specifi cations without notice.
Page 156
Set point displ., supply air Set point displ., extract air Analogue See Section 6.4.19 Inactive Set point displacement Input 2 Set point displ., supply air Set point displ., extract air www.swegon.com We reserve the right to alter specifi cations without notice.
Set point displ., supply air Set point displ., extract air Analogue See Section 6.4.19 Inactive Set point displacement Input 2 Set point displ., supply air Set point displ., extract air www.swegon.com We reserve the right to alter specifications without notice.
Temperature sensor no. 1 X Off Temperature sensor no. 2 X Off External communication module C X Off Temperature sensor no. 1 X Off Temperature sensor no. 2 X Off www.swegon.com We reserve the right to alter specifications without notice.
Page 159
Op. level communication Operation level X Inactive Total stop Total Stop Inactive Low speed Low speed High Speed High Speed Normal Stop Normal Stop Extended Normal Stop Extended Normal Stop www.swegon.com We reserve the right to alter specifi cations without notice.
Page 160
Wireless IQnavigator IP address IQnavigator Netmask Pre-selected IQnavigator gateway IQlogic IP address Brightness mode X Auto adjust Auto adjust Medium High Medium High Button sound effects X Off Volume www.swegon.com We reserve the right to alter specifi cations without notice.
Xzone, extract air temperature below set point alarm limit Xzone, cool, alarm input 1 tripped Xzone, cool, alarm input 2 tripped Cooling, valve monitoring tripped 10:1 Supply air temperature sensor defective www.swegon.com We reserve the right to alter specifications without notice.
15:14 Plate heat exchanger, defrosting sensor no. C communication error 15:15 Plate heat exchanger, defrosting pressure over alarm limit 16:1 Coil heat exchanger, I/O module no. 1 communication error 3)4) www.swegon.com We reserve the right to alter specifications without notice.
External communication, I/O module no. A temperature sensor no. 1 defec- tive 36:3 External communication, I/O module no. A temperature sensor no. 2 defec- tive 36:6 External communication, I/O module no. B communication error www.swegon.com We reserve the right to alter specifications without notice.
MIRU Control no. 5 pressure regulation sensor no. 1 communication error 42:6 MIRU Control no. 5 temperature sensor defective 42:7 MIRU Control no. 5 flow/pressure deviation from set point alarm limit www.swegon.com We reserve the right to alter specifications without notice.
Supply air fan no. 1A motor controller uneven phase voltage 49:8 Supply air fan no. 1A motor controller phase error 49:9 Supply air fan no. 1A motor controller internal memory error www.swegon.com We reserve the right to alter specifications without notice.
53:10 Supply air fan no. 2B motor controller current limitation 54:1 Supply air fan no. 3B communication error 54:2 Supply air fan no. 3B motor controller overcurrent 54:3 Supply air fan no. 3B motor controller undervoltage www.swegon.com We reserve the right to alter specifications without notice.
Extract air fan no. 3A motor controller internal memory error 57:10 Extract air fan no. 3A motor controller current limitation 57:11 Extract air fan no. 3A motor controller internal communication error 58:1 Extract air fan no. 1B communication error www.swegon.com We reserve the right to alter specifications without notice.
62:11 Extract air fan no. 3A I/O module communication error Cannot be blocked. The delay is adjustable. Adjustable. Stops the AHU if the temperature is below the adjustable limit. Inactive as factory setting. Commissioning performed by: Date Company Name www.swegon.com We reserve the right to alter specifications without notice.
Working points with less air flow is allowed to be found outside the permissible range e.g. in case of variable air flow. Max. limit, Ecodesign 2016. Outer limit - largest permissible air flow at maximum speed. Remaining outer limits. Recommended average working point. www.swegon.com We reserve the right to alter specifications without notice.
GB.GOLDSKE.160901 11.4 Building Materials Declaration For a complete Declaration of Construction Materials, see our home page at www.swegon.com under Products & Services. 11.5 License Copyright 2013-2014 Swegon AB All right reserved. Parts of this work is subject to GNU General Public License v2.0 and other Free/Libre Open Source Software licenses.
GB.GOLDSKE.160901 All documentation is available in digital form and can be downloaded from www.swegon.com www.swegon.com We reserve the right to alter specifications without notice.