3.5.1

Connection to the GOLD air handling unit,

version F
The sealing strips are factory-fitted to the unit.
Place the COOL DX Top on top of the GOLD air handling
unit according to Section 3.4 Basic installation diagram for
the COOL DX Top.
If lifting is required, use lifting eye bolts fastened to the
duct connections, see Section 3.2.3. After you've finished
lifting, remove the lifting eye bolts.
The guide pins are located on the top of the GOLD unit to
felicitate correct positioning during installation. See illus-
tration.
Dismantle the service hatch. When you've dismantled the
service hatch, remove and discard the cover plate located
inside the cooling unit. See illustration.
The GOLD unit's safety isolating switch is supplied loose
and is lying in the opening for the GOLD's electric equip-
ment cubicle and should be mounted in predrilled hole on
the COOL DX Top. See illustration.
Service hatch
Remove and
discard the cover
plate
Guide pins
3.5.2

Drainage/Water trap, version F

Connect the drain connection to the drain pipework via
a water trap, see separate instructions for the TBXZ-1-40
water trap.
We reserve the right to alter specifications.
GB.COOLDX.IN.G.200701
Predrilled hole for the
GOLD unit's safety switch
GOLD safety switch
www.swegon.com
15