4.5 Frost protection

Heating coil
The frost protection function is always active if the heating
coil has been correctly configured in the product setup.
The monitoring function uses the temperature sensor T7
for the integrated coil (IBA) or for the external coil (EBA).
The function is activated when the temperature of the coil
drops below 4°C. Under these conditions the pump output is
activated and the three-way valve output will be 100% and
the unit will shut down and generate a frost alarm.
PLATE HEAT EXCHANGER (PX)
There are four strategies to protect the plate heat exchanger
from freezing :
1 - Reduced supply air flow :
The heat exchanger is supplied with a frost
protection sensor on the exhaust air (T3). If the exhaust air
temperature (T3) is >1°C and <+5°C :
In airflow control mode and demand control, the supply
air flow will modulate between 100% and 33% (AFlow)of
the setpoint (AFn).
In pressure control mode, the supply air pressure will
modulate between 100% and 50% (AFlow) of the
setpoint (AFn).
If the exhaust air temperature (T3) is <1°C, the supply air
fans will stop until the exhaust air temperature (T3) is >2°C
for 5 minutes.
2 - Modulating bypass :
The modulating bypass is controlled by the exhaust
temperature sensor (T3). If:
Exhaust temperature (T3) >+1°C: bypass closed or
controlled by free cooling function.
Exhaust temperature (T3) ≤ +1°C: bypass will modulate
for the exhaust temperature (T3) to exceed +1°C.
The corresponding supply air temperature will drop due to a
lower airflow through the heat exchanger.
Requires a post-heating coil (IBA, KWout, EBA or 3rd part
delivered)
3 - Electrical preheating coil (accessory) :
If an electrical pre-heating coil (KWin) is installed and
configured, the pre-heating coil (KWin)will modulate so the
exhaust temperature is +1°C.
12
www.swegon.com
GB.ESENSA.MO.231025
4 - Differential pressure measurement (Cold climate
option) :
For cold climate conditions (>=-20⁰C), the unit is equipped
with a differential pressure sensor mounted on the heat
exchanger. The pressure sensor detects when the pressure
drop, due to frost, has become too high. In critical
conditions, the supply air flow will be paused for a short time,
to allow for defrosting.
The frost protection strategy (down regulation supply airflow,
modulating bypass or electrical pre-heating) will still be used
as a first step. The defrost function will only be active if the
frost protection strategy is not sufficient.
These Settings can be configured in ADVANCED SETUP
ROTARY HEAT EXCHANGER (RX)
In order to protect the rotary heat exchanger from freezing,
the strategy for frost protection consists of modulating the
speed of the rotating heat exchanger, which is linked to the
outdoor air temperature (sensor T1).
If the outdoor air temperature < T°AF (default -9°C): the
rotation speed of the heat exchanger is reduced to avoid the
risk of icing. To exit this anti-frost protection: T°(T1) ≥ T°AF for
5 minutes.
These Settings can be configured in ADVANCED SETUP.

4.6 Time Schedule

The controller allows 6 time slots (channels) to be
configured. For each day of the week, the operation mode
can be either AUTO (operate according to time slots) or
manual (selection of speed).
For each time slot select :
Start time
Operating mode
Speed selection: I, II, III for CA/TQ, normal/reduced for
LS/CP and, for all modes, boost level
Heating setpoint if postheater is present
Cooling setpoint if postcooler is present
We reserve the right to alter specifications.

5. Preventive maintenance

Attention : before handling and/or opening the access panels it is compulsory to shut down the unit and disconnect
the power supply using the general switch located on the front panel.
Do not isolate the power supply whilst the unit is running. If KWin and\or KWout are installed, then isolate the
corresponding power supplies.
Regular maintenance is essential to guarantee good operation of the air handling unit and a long service life. The maintenance
frequency will depend on the application and on the actual environment conditions but the following are general guidelines:
5.1 Once the unit operates in
normal condition
Replace the filters with a kit of replacement filters.

5.2 Every 3 months

Check for any alarms indicated on the control device. In case of
an alarm refer to troubleshooting section.
Check the state of filter clogging. The control device allows a
pre-defined 'filter alarm' threshold to be set. Replace filters
if necessary. Filters that are too clogged can generate the
following problems:
- Insufficient ventilation.
- Excessive increase of fan rotation speed.
- Excessive sound levels.
- Excessive power consumption (power consumption will
increase exponentially to an increase in pressure drop, for a
constant airflow).
- Unfiltered air passing through the heat exchanger
(risk of clogging) and into ventilated rooms.
The list of replacement filter kits for each unit can be
downloaded from our website.
- To locate the filter, refer to schemas on page 9 to 14.
- Inspection and cleaning of the inside of the unit:
• Vacuum clean any accumulations of dust in the unit.
• Inspect and gently vacuum clean the heat exchanger if
necessary. Use a brush to protect the fins.
• Clean any condensation stains.
• For PX units, clean any accumulations in the drain pan.
We reserve the right to alter specifications.
GB.ESENSA.MO.231025
www.swegon.com