We Reserve The Right To Alter Specifications Without Notice - Swegon GOLD RX Operation And Maintenance Instructions

Generation e rotary heat exchanger
Hide thumbs Also See for GOLD RX:
Table of Contents

Advertisement

Alarm text
Function
49-
SUPPLY AIR FAN 1-3/A-B MOTOR CONTROLLER MEMORY
54:9
ERROR
Internal memory error in motor controller.
49-
SUPPLY AIR FAN 1-3/A-B MOTOR CONTROLLER CURRENT
54:10
LIMITATION
Current/Voltage limitation in motor controller.
49-
SUPPLY AIR FAN 1A-3A MOTOR CONTROLLER INTERNAL
51:11
COMMUNICATION ERROR
Internal communication error in motor controller.
Alarm group 55-60: Extract air fan no. 1A-3B
55-
EXTRACT AIR FAN 1-3/A-B COMMUNICATION ERROR
60:1
The air handling unit's control unit cannot establish correct
communication with the extract air fan motor controller.
55-
EXTRACT AIR FAN 1-3/A-B MOTOR CONTROLLER OVERCUR-
60:2
RENT
High current supplied to motor
55-
EXTRACT AIR FAN 1-3/A-B MOTOR CONTROLLER UNDER-
60:3
VOLTAGE
Voltage below the normal level is supplied.
55-
EXTRACT AIR FAN 1-3/A-B MOTOR CONTROLLER OVERCUR-
60:4
RENT
Excessively high voltage is supplied.
55-
EXTRACT AIR FAN 1-3/A-B MOTOR CONTROLLER EXCESS
60:5
TEMPERATURE
High internal temperature.
55-
EXTRACT AIR FAN 1-3/A-B MOTOR CONTROLLER START UP
60:6
ERROR
Extract air fan does not rotate on a start up, rotates in
wrong direction or rotates at excessively high speed.
55-
EXTRACT AIR FAN 1-3/A-B MOTOR CONTROLLER UNEVEN
60:7
PHASE VOLTAGE
High voltage difference between the phases (3-phase, 400
V), which causes rippling.
55-
EXTRACT AIR FAN 1-3/A-B MOTOR CONTROLLER PHASE
60:8
FAILURE
Phase failure in motor controller.
55-
ETRACT AIR FAN 1-3/A-B MOTOR CONTROLLER MEMORY
60:9
ERROR
Internal memory error in motor controller.
55-
EXTRACT AIR FAN 1-3/A-B MOTOR CONTROLLER CURRENT
60:10
LIMITATION
Current/Voltage limitation in motor controller.
55-
EXTRACT AIR FAN 1A-3A MOTOR CONTROLLER INTERNAL
57:11
COMMUNICATION ERROR
Internal communication error in motor controller.
102
www.swegon.com
Priority
0 = Blocked 0 = In operat.
A = A alarm
B = B alarm
A
1)
B
A
9)
A
A
1)
A
1)
A
1)
A
1)
A
1)
A
1)
A
1)
A
1)
B
A

We reserve the right to alter specifications without notice.

GB.GOLDSKE.160901
Stop
Delay
s = second
1 = Stop
m = minute
h=hour
1
10 s
3)
0
60 s
3)
1
10 s
3)
1
10 s
3)
1
3 s
3)
1
3 s
3)
1
3)
3 s
1
3 s
3)
1
3 s
3)
1
3)
5 s
1
5 s
3)
1
5 s
3)
0
60 s
3)
1
5 s
3)
Resetting
0 = manual
1 = automatic
1
1
1
1
0
0
0
0
0
1
1
1
1
1

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gold pxGold cxGold sd

Table of Contents