Function Guide for the GOLD,
Xzone
1. General
The Xzone function is designed for controlling one extra
temperature zone via the ventilation system.
Sometimes it is necessary to control a part of the venti-
lation system with different temperature prerequisites.
This may be due to proximity to the perimeter wall of the
building facing north or south; workshop, office or other
conditions that give rise to different temperature loads in
various parts of a building.
The Xzone function can control one extra temperature
zone, max.
Xzone can be used for all types of GOLD air handling unit
with program version 5.00 or later, and both postheating
and cooling can be controlled in the extra zone.
When Xzone is activated, several menus appear in the
hand-held micro terminal under user level for setting and
reading the extra zone parameters.
The type of temperature control for the extra zone must
be selected separately, and can be of another type than
that used in the main zone.
If extract air temperature control is selected, the tem-
perature sensors must be positioned so that they will not
be influenced by the temperature in the other zone. This
means that the internal extract air sensor (inside the air
handling unit) must not be used for control for the main
zone. The room sensor or extra extract air sensor should
be used, (see TBLZ-1-30 or TBLZ-1-24 in section Material
Specification).
The air heater and air cooler for the main and extra zone
must be sized on the basis of separate computerized
calculations. Always take into account that the duct sys-
tem where the air heater and air cooler are fitted, does
not have the same dimensions as the connection spigots/
frames of the air handling unit.
We reserve the right to alter specifications.
2. Material Specification
Air handling unit:
Xzone Control box
Consists of: IQnomic Plus, TBIQ-2-1, heating
IQnomic Plus, TBIQ-2-1, cooling
Comm. cable BC1-1 (L=250mm)
Code: a 0 = Without freeze protection monitor sensor
1 = With freeze protection monitor sensor
b 1= With supply air temperature sensor
2 = With supply air and extract air temperature
sensor
3 = With supply air and room air temperature
sensor
cc 01 = With 1 metre long communication cable
03 = With 3 metre long communication cable
05 = With 5 metre long communication cable
10 = With 10 metre long communication cable
15 = With 15 metre long communication cable
Supply air temperature sensor, set (TBLZ-1-30), according
to selection above consists of the following:
Duct temperature sensor 32106304
Jack for wall mounting 019611
Extract air temperature sensor, set (TBLZ-1-30), according
to selection above consists of the following:
Duct temperature sensor 32106304
Jack for wall mounting 019611
Room temperature sensor (TBLZ-1-24), according to selec-
tion above.
When the heater is electric of type Swegon standard incl.
control cable:
Adaptor modular/terminal
GB.XZONE.080630
All types of GOLD
TBLZ-1-50-a-b-cc
TBLZ-1-55
www.swegon.com
1

Advertisement

loading

Summary of Contents for Swegon GOLD

  • Page 1 1 = With freeze protection monitor sensor zone, max. b 1= With supply air temperature sensor Xzone can be used for all types of GOLD air handling unit 2 = With supply air and extract air temperature with program version 5.00 or later, and both postheating sensor and cooling can be controlled in the extra zone.
  • Page 2: Operation

    Connect a cable for 0-10 V DC control of the valve actua- the GOLD air handling unit control unit. Connect the air tor cooling or air cooler for cooling in 1 - 3 steps or cool-...
  • Page 3: Electrical Connections

    Control of cooling step 2 Pump controls Supply voltage to 1-phase pump, max 1.5 A, can be obtained by wiring to the following terminals inside the GOLD air handling unit: Terminal 101 (L), terminal 102 (N). PE N L www.swegon.com...
  • Page 4 27 kW 230 V (Norway) demand can be obtained by wiring to the following supply voltage 24 VAC to internal control equip- terminals inside the GOLD air handling unit: ment. Supply voltage 24 VAC can be connected Terminal 101 (L), terminal 102 (N).
  • Page 5 GB.XZONE.080630 5. Adjustment. INSTALLATION For basic particulars on how to handle the hand-held FUNCTIONS micro terminal, see the Operation and Maintenance Instructions for the GOLD unit. *FUNCTIONS* TEMPERATURE FLOW/PRESSURE FILTER OPERATION The Xzone function must be manually activated, under HEATING INSTALLATION –...
  • Page 6 A new menu group XZONE is displayed between TEM- XZONE PERATURE and FLOW/PRESSURE under SETTINGS at user level. The selected temperature control function setpoint settings required for for the extra zone can be set there. *XZONE* READINGS SETTING www.swegon.com We reserve the right to alter specifications.
  • Page 7: Performance Checks

    IQnomic Plus module: 16 17 22 23 Light-emitting diode L2 lit with a steady glow indicates that power is being supplied from the GOLD unit’s control unit. A flashing light-emitting diode L1 indicates correct com- munication with the GOLD unit’s control unit.