6.2 Main Setup

Main setup can be selected when installing the AHU and is an
aid for confi guring and starting up the AHU.
Time and date, air fl ow unit, airfl ow regulation mode, airfl ow
operation level, temperature regulation, temperature settings
and fan position settings can be entered here.
For mosre detailed information, see the relevant function below.
See Section 6.4.3.1
See Sections 6.4.1.6 and 6.4.2.4
See Section 6.4.1.3
See Section 6.4.1.2
See Section 6.4.2.3
See Section 6.4.2.2
See Section 6.4.10.1
6.3 Filter Calibration
All the fi lters should be calibrated when the fans are started up
for the fi rst time and when the duct system, air terminals and
commissioning plates, if required, have been installed and com-
missioned.
After that every time fi lters are replaced. Calibration should then
be activated for the fi lter or fi lters that are new. Relevant fi lters
are the Supply air prefi lter, Extract air pre-fi lter, Supply air AHU
fi lter, Extract air AHU fi lter, SA and EA AHU fi lter and Supply air
end fi lter.
When fi lter calibration is activated, the air handling unit runs at
the preset max. speed (depending on the functionality selected)
for about 70 seconds.
After the fi lters have been calibrated, a pressure rise of up to 100
Pa is permissible (as the fi lters arrest impurities) after which an
alarm indicating fouled fi lter is initiated. The alarm limit can be
changed under Installation, Functions, Filters.
The fi lter function must be activated (see Section 6.4.5) in order
to make it possible to enable fi lter calibration and alarm func-
tions of the end fi lter and pre-fi lter in GOLD SD supply air and
extract air handling units.
32
www.swegon.com
Main setup
Main setup
1 Time and date
2 Air fl ow unit
3 Air fl ow regulation
mode
4 Air fl ow operation level
5 Temperature regulation
6 Temperature settings
7 Fan position
8 Finish
Filter calibration
Filter calibration
Supply air pre-fi lter
Extract air pre-fi lter
SA and EA pre-fi lter
We reserve the right to alter specifi cations without notice.
GB.GOLDSKE.160901
TIME AND DATE
Time
Date
Wednesday
Weekday
Time zone
CALIBRATION MODE
Supply air AHU fi lter
Extract air AHU fi lter
SA and EA AHU fi lter
Supply air end fi lter
Progress
Start