Alarm text
Function
4:3
EXTRA REGULATION SEQUENCE 1, FROST GUARD TRIPPED
Frost guard temperature sensor measures temperature less
than preset alarm limit.
Factory setting: 7 °C.
4:4
EXTRA REGULATION SEQUENCE 1, FROST GUARD TEMPER-
ATURE SENSOR DEFECTIVE
Frost guard temperature sensor is defective or is not con-
nected.
4:5
EXTRA REGULATION SEQUENCE 1, VALVE MONITORING
TRIPPED
Valve actuator, air heater for water, is defective.
4:6
EXTRA REGULATION SEQUENCE 1, ALARM INPUT TRIPPED
Alarm input extra regulation sequence has tripped.
4:7
EXTRA REGULATION SEQUENCE 1, TEMPERATURE PROTEC-
TION VIA COMMUNICATION, COMMUNICATION ERROR
The air handling unit's control unit is not receiving any tem-
perature reading via the external communication interface
within the preset time limit.
4:9
EXTRA REGULATION SEQUENCE 2, I/O-MODULE No F
COMMUNICATION ERROR
The air handling unit's control unit cannot establish correct
communication with I/O module No. E for extra regulation
sequence.
4:10 EXTRA REGULATION SEQUENCE 2, OVERHEATING PROTEC-
TION FOR ELECTRIC AIR HEATER TRIPPED
Overheating protection, electric air heater, has tripped.
4:11 EXTRA REGULATION SEQUENCE 2, FROST GUARD TRIPPED
Frost guard temperature sensor measures temperature less
than preset alarm limit.
Factory setting: 7 °C.
4:12 EXTRA REGULATION SEQUENCE 2, FROST GUARD TEMPER-
ATURE SENSOR DEFECTIVE
Frost guard temperature sensor is defective or is not con-
nected.
4:13 EXTRA REGULATION SEQUENCE 2, VALVE MONITORING
TRIPPED
Valve actuator, air heater for water, is defective.
4:14 EXTRA REGULATION SEQUENCE 2, ALARM INPUT TRIPPED
Alarm input extra regulation sequence has tripped.
Alarm group 5: Reheating
5:1
REHEAT, OVERHEATING PROTECTION FOR ELECTRIC AIR
HEATER TRIPPED
The overheating protection, electric air heater, has tripped.
5:2
REHEAT, FROST GUARD TRIPPED
Frost guard temperature sensor measures temperature less
than preset alarm limit.
Factory setting: 7 °C.
5:3
REHEAT, FROST GUARD TEMPERATURE SENSOR DEFECTIVE
Frost guard temperature sensor is defective or is not con-
nected.
5:4
REHEAT, VALVE MONITORING TRIPPED
Valve actuator, air heater for water is defective.

We reserve the right to alter specifications without notice.

Priority
Stop
0 = Blocked 0 = In operat.
A = A alarm
1 = Stop
B = B alarm
A
1
1)
A
1
1)
B
0
3)
A
0
B
0
A
0
3)
A
1)
0
3)
A
1
1)
A
1
1)
B
0
3)
A
0
A
0
1)
3)
A
1
1)
A
1
1)
B
0
3)
GB.GOLDSKE.160901
Delay
Resetting
s = second
0 = manual
m = minute
1 = automatic
h=hour
5 s
0
3 s
1
10 m
0
20 s
0
5 m
1
10 s
1
10 s
0
5 s
0
3 s
1
10 m
0
20 s
0
10 s
0
5 s
0
3 s
1
10 m
0
www.swegon.com
89