Swegon GOLD SD Description

Swegon GOLD SD Description

Air handling unit

Advertisement

Description of the air handling unit
GOLD PX
GOLD SD
General, Range of Application, Certifi cation ................................................................... 2
Mechanical Design ............................................................................................................. 3
Electrical and Control Equipment ..................................................................................... 9
Hand-Held Micro Terminal and How to Use the Menus ................................................ 10
Control Schedule ............................................................................................................... 11
Delivery Version ................................................................................................................ 16
Installation Tips ................................................................................................................ 23
Contents
20190329
GOLD RX
GOLD CX
We reserve the right to alter specifi cations.
GOLD
1

Advertisement

Table of Contents
loading

Summary of Contents for Swegon GOLD SD

  • Page 1: Table Of Contents

    GOLD Description of the air handling unit GOLD PX GOLD RX GOLD SD GOLD CX Contents General, Range of Application, Certifi cation ..............2 Mechanical Design ......................3 Electrical and Control Equipment ..................9 Hand-Held Micro Terminal and How to Use the Menus ..........10 Control Schedule .......................
  • Page 2: General, Range Of Application, Certifi Cation

    (PX) or coil heat exchanger (CX). GOLD units equipped with counterfl ow-/coil heat The GOLD SD single-direction units are supply air/extract exchanger (PX/CX) and separate supply air and extract air air handling units with one direct-driven supply air or handling units (SD) can also be used for the ventilation extract air fan.
  • Page 3: Mechanical Design

    Composed of flush-mounted cover panels and inspec- tion doors. The outer skin is made of galvanized sheet steel, re-painted in Swegon’s own grey metallic paint (closest comparable RAL colour: 9007). The inner skin is made of aluminium-zinc plated sheet steel. The entire air handling unit conforms to Environmental Class C4.
  • Page 4 Circular duct connections for insertion joints fi tted with a rubber seal ring as standard. The GOLD SD size 004-008 without coil heat exchanger can be mounted on base beams, a foundation or on a stand. Prefi tted base beams are obtainable as optional equipment;...
  • Page 5 60% (M5) or ePM1 50% (F7) filters. GOLD RX Top size 004-012 is equipped with pleated filters. The separate GOLD SD supply air and extract air handling units in sizes 004-012 in a common casing can have pleated filters as an option.
  • Page 6 GOLD Description of the Air Handling Unit Mechanical Design Heat exchanger Rotary heat exchanger RECOnomic/RECOsorptic rotary heat exchanger with a temperature effi ciency of up to 85%. The need for heat is dealt with by automatically and variably regulating the speed of the rotor.
  • Page 7 GOLD Description of the Air Handling Unit Mechanical Design Coil heat exchanger The coil heat exchanger in the one-piece units, GOLD CX, sizes 035-080, are supplied complete from the fac- tory; including mounted pipework package with all the necessary components. The system is normally fi lled with liquid, vented, adjusted and performance-tested prior to delivery, but can also be ordered in unfi lled condition e.g.
  • Page 8 Environment Declaration Swegon AB has a certifi cated environmental management system that conforms to ISO 14001 Standard and is regis- tered on the REPA Register, no. 5560778465.
  • Page 9: Electrical And Control Equipment

    Control Unit – GOLD SD and the size 035-080 GOLD CX units, electrical and If both GOLD SD supply air and extract air handling units control equipment must be wired via the panel on the are used in a ventilation system, the supply air unit is centre section of the air handling unit.
  • Page 10: Hand-Held Micro Terminal And How To Use The Menus

    GOLD Description of the Air Handling Unit Hand-held micro terminal IQnavigator and image management The IQnavigator hand-held micro terminal, has 7" touch- screens and is very simple and user friendly. Commis- sioning and the entering of settings can be carried out intuitively and in steps.
  • Page 11: Control Schedule

    GOLD Description of the Air Handling Unit Control Schedule Diagrammatic description of the control functions, GOLD RX The built-in control system controls and regulates temper- atures, airflows, in-operation periods and a large number When you use the AHU Design air handling unit selection program for calculating data, you receive a project-specific flow of internal and external functions.
  • Page 12 GOLD Description of the Air Handling Unit Control Schedule Diagrammatic description of the control functions, GOLD PX The built-in control system controls and regulates temper- When you use the AHU Design air handling unit selection atures, airflows, in-operation periods and a large number program for calculating data, you receive a project-specific flow of internal and external functions.
  • Page 13 GOLD Description of the Air Handling Unit Control Schedule Diagrammatic description of the control functions, GOLD CX The built-in control system controls and regulates temper- atures, airflows, in-operation periods and a large number When you use the AHU Design air handling unit selection of internal and external functions.
  • Page 14 Description of the air handling unit Control Schedule Diagrammatic description of the control functions, GOLD SD sizes 004-012, common casing The built-in control system controls and regulates temper- atures, airflows, in-operation periods and a large number When you use the AHU Design AHU selection program for of internal and external functions.
  • Page 15 Description of the air handling unit Control Schedule Diagrammatic description of the control functions, GOLD SD, sizes 004-012 in split version and sizes 014-120 The built-in control system controls and regulates temper- atures, airflows, in-operation periods and a large number When you use the AHU Design AHU selection program for of internal and external functions.
  • Page 16: Delivery Version

    The max. length of a delivery unit is 3,000 mm. • An air handling unit arrangement may at most be divided into four delivery units (sizes 004-060). See also Swegon's air handling unit software: AHU Design. We reserve the right to alter specifications. 20190329...
  • Page 17: Possible Combinations For Filter/Fan Sections, Rx, Size 014-030

    GOLD Description of the unit Possible combinations for filter/fan sections, RX, size 014-030 Note that performance, dimensions and weight are dif- Filter/fan sections for basic variants of standard RX and ferent depending on whether the filter/fan section is RX Top can be combined in a number of different ways, RX standard or RX Top, see section Sizing, installation, see below and the next page.
  • Page 18 GOLD Description of the unit Possible combinations for filter/fan sections, RX, size 014-030 Combinations Left-hand version Right-hand version Standard Standard Standard Standard Standard Standard Standard Standard Outdoor air Supply air Extract air Exhaust air Option Option Option Option outdoor air supply air extract air exhaust air...
  • Page 19: Possible Combinations For Filter/Fan Sections, Px, Size 004-008

    GOLD Description of the unit Possible combinations for filter/fan sections, PX, size 004-008 These side fed filter/fan sections have the same perfor- PX Top size 004-008 has, from PX standard side fed air mance as a PX standard side fed filter/fan section, see the handling units, a deviating height measurement.
  • Page 20 GOLD Description of the unit Possible combinations for filter/fan sections, PX, size 004-008 Dimensions The diagrams show side fed filter/fan sections with a height measurement adapted to each size of PX Top and centre section. Filter/fan section to the left of the centre section Filter/fan section to the right of the centre section ø...
  • Page 21: Possible Combinations For Filter/Fan Sections, Px, Size 011-030

    GOLD Description of the unit Possible combinations for filter/fan sections, PX, size 011-030 Note that performance, dimensions and weight are dif- Filter/fan sections for basic variants of standard PX and PX ferent depending on whether the filter/fan section is PX Top can be combined in a number of different ways, see standard or PX Top, see section Sizing, installation, dimen- below and the next page.
  • Page 22 GOLD Description of the unit Possible combinations for filter/fan sections, PX, size 011-030 Combinations Left-hand version Right-hand version Standard Standard Standard Standard Outdoor air Supply air Extract air Exhaust air Option Option outdoor air extract air We reserve the right to alter specifications. 20190329...
  • Page 23: Installation Tips

    Examples of how air deflectors and extruded inlets minimize pressure losses in Swegon accessories for the GOLD. If the use of a common outdoor air duct is still desirable, every branch duct for each GOLD air handling unit must be equipped with a non- return damper or a motorized damper (also applies to a common exhaust air duct/hood).
  • Page 24 GOLD We reserve the right to alter specifications. 20190329...