6.4.3 Time and schedule

The built-in timer enables you to control the AHU's operating
mode/time. Certain other oversteering functions such as external
timer, communication, etc. affect the preset operating modes.
There are fi ve different operating modes:
Total stop = The AHU is completely stopped, no internal auto-
matic functions or external control commands can start the AHU.
Normal Stop = The AHU has stopped, however all the internal
and external automatic functions oversteer the stop.
Extended Normal Stop = The AHU has stopped, however all the
internal and external automatic functions, with exception of
Summer night cool, oversteer the stop.
Low speed = The AHU is running at the preset low speed setting.
High speed = The AHU is running at the preset high speed set-
ting.
6.4.3.1 Time and date
The current date and time can be set and adjusted if needed. The
timer automatically takes leap years into consideration.
The relevant region and city can be selected, summer time/winter
time changover will then be managed automatically.
Time source can be set to manual or via SNTP (requires connec-
tion to network) and BACnet. The time format and date format
can be set.
6.4.3.2 Schedule settings
The relevant operating mode can be read under Schedule set-
tings. Here you can also set a preselected operating mode, in
which the air handling unit always operates during non-pro-
grammed time, under Day schedule and Exceptions schedule.
This setting (start and stop date not activated) is used most often
and covers the majority of needs.
When the start and stop date is activated, this means that dur-
ing the preset period (date) preset time applies during the day
schedule and the exceptions schedule, and at all other times the
AHU runs in the preselected operating mode.
Settings:
Value
Preselected operating
mode
Start date
Start date
Stop date
Stop date
50
www.swegon.com
Setting
Factory
range
settings
Total stop/Low
Low speed
speed/High speed/
Normal Stop/
Extended Normal
Stop
Active/Inactive
Inactive
Year/Month/Day
Active/Inactive
Inactive
Year/Month/Day
Time and
schedule
Time and date
Schedule settings
We reserve the right to alter specifi cations without notice.